Page 36
IPL T SF Series Interfaces • Software Setup
Software Setup, cont’d
3-16
If the Flex I/O mode is Analog Input
4
.
Enter a unique description.
5
.
Select the analog input options.
• Unit Label — Identify the units (ex: "C" for degrees
centigrade) that the following values will represent
when displayed in the GlobalViewer interface.
• Show Values as Voltage — If this radio button is
selected, the analog voltage input value to the Flex
I/O port is displayed in GlobalViewer and the Custom
Value options (below it) will not be active.
• Show Custom Values — If this radio button is selected,
you can set a scale of relative values that will display
the desired numeric values in the GlobalViewer
interface.
• Example: If you want an input of 4 volts to represent
a temperature of 0˚ C, and an input of 24 volts to
represent a temperature of 100˚C
•
Enter "C" (for Centigrade) in the Unit Label field.
•
Set the Lower voltage slider at 4.0, and enter 0 in it's
Value field.
•
Set the Upper voltage slider at 24.0, and enter 100 in
it's Value field.