5

2.4

Remote partial reset connection


Terminal


11

Anode.

12

Cathode.


This input is for connecting a remote push button to reset the partial volume counter, which is

used principally for starting batching processes. These terminals are configured to be activated by a
potential free normally open push button.

The reset input can be connected to the input of an opto-isolator as shown below. The

minimum current required to activate this input is about 2 mA, which can be obtained by applying a

minimum voltage of 5 Vdc to the input. (+ to terminal 11 and – to terminal 12). To do this the instrument
must be opened at the front, the printed circuits must be withdrawn and the JP1 and JP2 jumpers
must be changed to position 1-2.

The push button contact must be a good quality snap action switch to guarantee correct working at low
voltages and reduce contact bounce to a minimum.

2.5

Connection of digital outputs

The digital outputs are NPN opto-isolated bipolar transistors with the same characteristics as the
pulse output (see part 2.3).


Terminal


4

Collector output 1.

5

Emitter output 1.

6

Collector output 2.

7

Emitter output 2.


In the event of employing inductive loads, such as relays, the use of a free wheeling diode is

necessary and should be connected (see part 2.3).