Tecfluid FLOMID-MX User Manual
Page 11

11
P
u l s e w i d t h
6 5 m s
After the option is chosen, the set-up returns to the main menu. Pressing the
push button
the next item on the main menu is displayed
4.3 Analog
output
A n a l o g o u t p u t
This is a 4 – 20 mA output proportional to the flow rate. To configure the beginning and end of
the scale the
push button must be pressed.
4.3.1
Beginning of scale
This is the flow rate value corresponding to the beginning of the analog scale (4 mA).
B
e g . o f s c a l e
> 0 0 0 0 0 0 0 l / h
The flow rate is entered in the measuring units programmed as in part 4.1.3.
4.3.2
End of scale
This is the flow rate value corresponding to the end of the analog scale (20 mA).
If a value for the full scale which is equal or less than the beginning of the scale is introduced,
then this value will not be accepted and the cursor will go back to the first digit.
E
n
d o f s c a l e
> 0 0 0 7 0 0 0 l / h
Once the analog scale has been configured the set-up returns to the main menu.
Pressing
the
push button the next item on the main menu is displayed
4.4 Digital
outputs
D i g i t a l
o u t p u t s
Pushing the
push button we access the sub menu to configure the two digital outputs.