TE Technology TC-36-25-RS232 User Manual
Page 47
6. OUTPUT CURRENT COUNTS
Write Command:
NA
Read Command: 07
Interpret:
Output current detection in A/D counts.
7. ALARM TYPE
Write Command: 28
Read Command: 41
Interpret:
0 sent or returned means no alarms.
1 sent or returned means Tracking Alarm Mode.
2 sent or returned means Fixed Alarm Mode.
3 sent or returned means Computer Controlled Alarm Mode (see write
command ALARM LATCH ENABLE).
8. SET TYPE DEFINE (the desired control temperature or “set temp” input definition)
Write Command: 29
Read Command: 42
Interpret:
This function tells the controller how the set-point will be communicated.
0 sent or returned means computer communicated set value.
1 sent or returned means Potentiometer Input.
2 sent or returned means 0 to 5 V Input.
3 sent or returned means 0 to 20 mA Input.
4 sent or returned means “Differential set”: Desired Control Value = Temp2 +
Computer Set.
5 sent or returned means set value is from optional MP-2986 Display and
Keypad accessory.
The range of values is settable via the commands HIGH EXTERNAL SET RANGE
and LOW EXTERNAL SET RANGE.
9. SENSOR TYPE
Write Command:
2a
Read Command: 43
Interpret:
0: TS141 5K
1: TS67 OR TS136 15K
2: TS91 10K
3: TS165 230K
4: TS104 50K
5: YSI H TP53 10K
10. CONTROL TYPE
Write Command: 2b
Read Command: 44
Interpret:
0 is deadband control.
1 is PID control.
2 is computer control.
11. CONTROL OUTPUT POLARITY
Write Command: 2c
Read Command: 45
Interpret:
0 is HEAT WP1+ and WP2-.
1 is HEAT WP2+ and WP1-.
12. POWER ON/OFF
47