4.0)

MINIMUM CLEARANCES TO COMBUSTIBLES

Failure to do so may result in death, serious injury or

property damage.

Combustible material must be located outside the

clearance dimensions listed.

Follow the instructions packaged with the kit for installation. Install the warnings card (ordered separately) and
complete the blank spaces using the clearances from combustibles table below. See Section 27 for a printed
copy of the warnings card.

Minimum clearances to combustibles shall be measured from the outer surfaces as shown in the following
diagram:

End

End

Ceiling

Below

Front

Rear

45° Angle (Maximum)

* Ceiling

Below

Side

Side

Horizontal

MINIMUM CLEARANCES TO COMBUSTIBLES

MINIMUM CLEARANCES TO COMBUSTIBLES

MINIMUM CLEARANCES TO COMBUSTIBLES

MINIMUM CLEARANCES TO COMBUSTIBLES

Model No.

Model No.

Model No.

Model No.

Mounted Horizontally

Mounted Horizontally

Mounted Horizontally

Mounted Horizontally

Angle Mounted at

Angle Mounted at

Angle Mounted at

Angle Mounted at

45º

45º

45º

45º

Sides

Sides

Sides

Sides

Ceiling*

Ceiling*

Ceiling*

Ceiling*

Below

Below

Below

Below

Ends

Ends

Ends

Ends

45º Front

45º Front

45º Front

45º Front 45º Rear

45º Rear

45º Rear

45º Rear

LTS 40, 50

24”

6”

40”

15”

40”

12”

LTS 60, 75

24”

6”

60”

15”

52”

12”

LTS/LTU 80, 90

26”

6”

66”

15”

52”

12”

LTS/LTU 100

28”

6”

76” **

15”

60”

12”

LTS/LTU 110, 120, 125, 130

32”

6”

82” **

20”

66”

12”

LTS/LTU 140, 150

36”

6”

87” **

20”

70”

12”

LTS/LTU 160, 175

42”

6”

93” **

20”

77”

12”

LTS/LTU 180, 200

44”

6”

106” **

20”

84”

12”

LTS/LTU 225, 250

56”

6”

112” **

20”

90”

18”

* When used indirect vented, minimum clearance for CEILING must be: 12” for LTS 40-75 and 18” for LTS/LTU
80-250. If optional corner and U-bend reflectors are not used, the clearance must be 18”.

** Maximum clearance below reduces by 50% once you are 25 ft. downstream from the burner box.

▲WARNING:

▲WARNING:

▲WARNING:

▲WARNING: Certain materials or objects, when stored under the heater, will be subjected to radiant heat and

Certain materials or objects, when stored under the heater, will be subjected to radiant heat and

Certain materials or objects, when stored under the heater, will be subjected to radiant heat and

Certain materials or objects, when stored under the heater, will be subjected to radiant heat and

could be seriously damaged.

could be seriously damaged.

could be seriously damaged.

could be seriously damaged. Observe the Minimum Clearances to Combustibles listed in the manual and on the

Observe the Minimum Clearances to Combustibles listed in the manual and on the

Observe the Minimum Clearances to Combustibles listed in the manual and on the

Observe the Minimum Clearances to Combustibles listed in the manual and on the

heater at all times.

heater at all times.

heater at all times.

heater at all times.

NOTE:

NOTE:

NOTE:

NOTE:

1.

1.

1.

1. The clearan

The clearan

The clearan

The clearances specified above must be maintained to combustibles and other materials that may be

ces specified above must be maintained to combustibles and other materials that may be

ces specified above must be maintained to combustibles and other materials that may be

ces specified above must be maintained to combustibles and other materials that may be

damaged by temperatures 90ºF above ambient temperature.

damaged by temperatures 90ºF above ambient temperature.

damaged by temperatures 90ºF above ambient temperature.

damaged by temperatures 90ºF above ambient temperature. Clearances to combustibles are posted on the

Clearances to combustibles are posted on the

Clearances to combustibles are posted on the

Clearances to combustibles are posted on the

control box.

control box.

control box.

control box. In areas used for storage of combustible materials wher

In areas used for storage of combustible materials wher

In areas used for storage of combustible materials wher

In areas used for storage of combustible materials where they may be stacked below the heater,

e they may be stacked below the heater,

e they may be stacked below the heater,

e they may be stacked below the heater,

NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height

NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height

NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height

NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height
to maintain the required clearances from the heater to combustibles.”

to maintain the required clearances from the heater to combustibles.”

to maintain the required clearances from the heater to combustibles.”

to maintain the required clearances from the heater to combustibles.” Space

Space

Space

Space----Ray recommends posting these

Ray recommends posting these

Ray recommends posting these

Ray recommends posting these

s

ss

signs adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.

igns adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.

igns adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.

igns adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.

2. The stated clearance to combustibles represents a surface temperature of 90

2. The stated clearance to combustibles represents a surface temperature of 90

2. The stated clearance to combustibles represents a surface temperature of 90

2. The stated clearance to combustibles represents a surface temperature of 90 ºF

ºF

ºF

ºF (32

(32

(32

(32 ºC) above room

ºC) above room

ºC) above room

ºC) above room

temperature. Building materials with a low heat to

temperature. Building materials with a low heat to

temperature. Building materials with a low heat to

temperature. Building materials with a low heat tolerance (such as plastics, vinyle siding, canvas, tri

lerance (such as plastics, vinyle siding, canvas, tri

lerance (such as plastics, vinyle siding, canvas, tri

lerance (such as plastics, vinyle siding, canvas, tri----ply, etc.)

ply, etc.)

ply, etc.)

ply, etc.)

may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent

may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent

may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent

may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent
materials are protected from degradation.

materials are protected from degradation.

materials are protected from degradation.

materials are protected from degradation.

This manual is related to the following products: