In multiple heater applica
multiple heater applica
multiple heater applica
multiple heater applications
tions
tions
tions, the combustion air intake may be ducted individually or common ducted in the
same configuration as shown for venting in Section 17.0). For combustion air intake duct sizing, please refer to
the Vent Sizing Table
Vent Sizing Table
Vent Sizing Table
Vent Sizing Table and use the diameter indicated, based on the number of heaters per duct.
Flue vent termination
must be 1 ft. (30cm)
higher than combustion
air inlet cap
Perforated Cover
(Remove)
The combustion air inlet should
be not less than 3 ft. (0.9m),
either vertically or horizontally,
from the flue vent termination.
Combustion Air Cap
(Leslie VersaCap
Type B)
6 Diameter
Single-Wall Pipe
Flashing
1/4 (6mm) fall per ft. (0.3m)
toward vent terminal
Horizontal
Through Sidewall
6 (15cm)
Minimum
6 Starting Collar
(field supplied)
3 ft. (91cm)
Minimum
Vertical
Through the roof
Control Box
Perforated Cover
(Remove)