Seaward Power Clamp User Manual
Page 28
![background image](https://www.manualsdir.com/files/804184/content/doc028.png)
27
(6) Inrush Current :
Function
Range
Accuracy
ACA
99.99A
± (2.5% + 0.2A)
599.9A
± (2.5% + 5dgt)
Overload protection : 1000 V
rms
/ 600 A
rms
Accuracy defined for :
Sine wave, ACA≧10Arms, Freq. 50/60Hz
- Integration time about 100m sec
(7)Active Power : Watt (DC/AC)
Function
Range
Accuracy
9.999 kW*
A,error×V,reading+
V,error×A,reading
99.99 kW
599.9kW
ACW / DCW
* The measured value<1.000kW,add 10 dgt to the accuracy.
Overload protection : 1000 V
rms
/ 600 A
rms
Accuracy defined for :
ACW :
Sine wave , ACV≧ 10 Vrms, ACA≧ 5 Arms
Freq. 50~60Hz, PF=1.00
DCW :
DCV ≧ 10V , DCA ≧ 5 A
(8) Power Factor
Function
Range
Accuracy
PF
-1.00 ~ 0.00 ~1.00
±3°±1dgt
Overload protection : 1000 V
rms
/ 600 A
rms