KD1E Range

Operating Instructions

14

9.0 Proof

Testing

9.1

Features of a PH3 Proving Unit

9.1.1 The terminations on the unit comprise of a knurled

earth terminal at one end and a small test point on

the top of the unit. The PH3 is available with a

test point designed to mate with either a domed or

a

fl at contact electrode type. Refer to section 3.1.

9.1.2 A push switch operates the test voltage output.

9.1.3 The unit requires an alkaline PP3 type battery,
also

identifi ed as a MN1604 and with the IEC

identifi er 6LR61.

9.1.4 Ensure that the red LED on the proving unit

operates before and after the unit has been used.

Warning – Do not touch the earth terminal and
the brass tip on the proving unit simultaneously.
When the push button is pressed 1.3KV is
generated between these points.

9.2

Testing Potential Indicators using a PH3 Proving Unit.

9.2.1 Type digital indicator. Using the 6 pin plug on

the base of the potential indicator connect the

insulating earth cable to the indicator and

securely

fasten.

9.2.2 The earth clamp attached to the free end of the

insulated earth cable should be attached to the

knurled earth terminal on the proving unit.