16.1 Factory Set Test Sequences

Test

Visual

Earth Continuity

Insulation

PE Conductor

Current

Touch Current

Substitute

Leakage

Wiring

RCD

Trip

Time

Name

Duration

(s)

Limit

()

Duration

(s)

Voltage

Limit

(M)

Duration

(s)

Limit

(mA)

Duration

(s)

Limit

(mA)

Duration

(s)

Limit

(mA)

Limit

(ms)

Portable/Handheld/IT CLI

Yes

5

0.1

2

500

1

Portable/Handheld/IT CLII

Yes

2

500

2

Fixed Appliance CLI

Yes

2

0.1

5

500

1

Fixed Appliance CLII

Yes

5

500

2

IEC Lead 2m

Yes

5

0.2

2

500

1

Yes

13A 5m Surge Protected Lead

Yes

5

0.2

2

250

1

Yes

13A 25m Ext Lead 30mA RCD

Yes

5

0.5

5

0.8

30

Portable CLI PE Current

Yes

5

0.5

2

250

1

5

0.8

Portable CLII Touch Current

Yes

2

250

2

5

0.3

IT Equip CLI PE Current

Yes

5

0.1

2

250

1

5

3.5

IT Equip CLII T ouch Current

Yes

2

250

5

0.3

13A 6m Mains Lead

Yes

5

0.2

2

500

1

Yes

13A 12m Mains Lead

Yes

5

0.3

2

500

1

Yes

13A 24m Mains Lead

Yes

5

0.5

2

500

1

Yes

Mov/Stat CLI 500V Insulation

Yes

5

0.1

2

500

1