15. Electrical Specification
Earth Continuity
Output Current (Load 2Ω):
Test Voltage (o/c) :
Measuring Range:
Display Range:
Resolution:
Operating Error:
Number of tests as per IEC61557-
4:
+/- 200mA DC with ZAP
> 4VDC
0.05Ω – 19.99Ω
0.01Ω – 19.99Ω
0.01Ω
+/-5% + 2 counts
approx 1,500.
Insulation Test
Test Voltages:
Test Current:
Test Voltage Accuracy:
Measuring Range:
Display Range:
Resolution:
Operating Error:
Number of tests as per IEC61557-
2:
500V and 250V DC
1mA minimum for a load of 1kohm/volt,
<2mA into s/c
+20%, -0%
0.10MΩ to 19.99MΩ
0.00MΩ to 19.99MΩ
0.01MΩ
+/-5% +5 counts (0.10MΩ to 9.99MΩ)
+/-10% +5 counts (10.00MΩ to 19.99MΩ)
approx 1,500.
Subsitute Leakage Test
Test Voltages:
Measuring Range:
Display Range:
Resolution:
Operating Error:
>25Vac <50Vac
0.20mA to 19.99mA
0.00mA to 19.99mA
0.01mA
+/-10% +2 digits
Protective Conductor Current
Test Voltage:
Display Range:
Measurement Range:
Resolution:
Operating Error:
Frequency Response:
Supply Voltage, maximum
load current 16A
0.01mA to 19.99mA
0.25mA to 19.99mA
0.01mA
+/-5% of reading +/- 3 digits
40Hz to 2.5 kHz
Touch Current
Test Voltage:
Display Range:
Measurement Range:
Resolution:
Operating Error:
Frequency Response:
Supply Voltage, maximum
load current 16A
0.00mA to 3.50mA
0.10mA to 3.50mA
0.01mA
+/-5% of reading +/- 2 digits
DC to 2.5 kHz