Service Diagnosis

Problem or Symptom

Possible Cause

Probable Correction

Poor Harvest

Scale in water system.

Clean water system.

Water or Air Temperatures too
cold

Check temps. Unit cannot
operate with water and air
temps below stated limits.

Low system charge

Recover and weigh charge.

Bypass solenoid does not open

Check solenoid operation

Check valve leaks back

Replace check valve

Hot gas valve does not open

Check for power to the coil, if
there is power, replace the hot
gas valve

Head pressure control valve
does not maintain enough
pressure (in freeze)

Replace the head pressure
control valve

Low capacity

High discharge pressure, from
a dirty condenser or faulty fan
motor

Clean the condenser, repair the
fan motor

Extreme hot location

Relocate the cabinet

Extremely hot condenser
location

Move condenser or provide
shade

Overcharge of refrigerant

Recover, evacuate and weigh
in the nameplate charge

Hot gas valve leaks thru, unit
off on refrigeration error

At the end of the freeze cycle,
there should be a definite
difference in temperature
between the inlet and outlet of
the Hot Gas Valve. If not,
replace the hot gas valve

Liquid and discharge lines are
in contact with each other

Separate and insulate them

Compressor cycles on and off

Compressor overheats

Low on refrigerant, locate leak,
recover refrigerant, repair leak,
replace drier, evacuate and
weigh in the nameplate charge.

TXV superheat too high, check
charge, if charge is OK, replace
TXV

Mechanical fault with
compressor, replace
compressor

Internal relief valve opened,
check for cause of high
discharge pressure

CME2006R