Remko heat pump manager, System selection – REMKO Multi-talent Plus User Manual
Page 46

REMKO Heat Pump Manager
System selection
12 basic hydraulic configurations
are provided in the heat pump
manager which can be pulled up
with the system selection and ap-
plied in the controller.
Pulled up with the system selection
and applied in the controller.
The system selection was decided in
accordance with the following criteria:
1. by type of heat pump
- only heating series:
CMF 80, CMF 140
- Heating/cooling series:
CMF 90/150/120/160,
CMT 100/150/120/160
CMF 120/160
System
selection
Functions
1
Basic hydraulics for the functions “Heating and hot water”, single energy-source mode, 1 supple-
mental electric heating, bivalence point -5°C
2
not for heat pumps with heating meters
3
not for heat pumps with heating meters
4
not for heat pumps with heating meters
5
not for heat pumps with heating meters
6
Heating/cooling version, single energy-source mode, 1 supplemental electric heating,
Bivalence point -5°C
7
Heating/cooling version, single energy-source mode, 1 supplemental electric heating, solar system,
bivalence point -5°C
8
not for heat pumps with heating meters
9
not for heat pumps with heating meters
10
Heating/cooling version, bivalent mode, bivalence point -3°C
11
Heating/cooling version, bivalent mode, solar system, bivalence point -3°C
12
Heating/cooling version, bivalent mode with solid fuel + option for 1 supplemental electric heating,
bivalence point -3°C
2. by operating mode
- single energy source
operation (supplemental
heating is a supplemental
electric heater)
- bivalent mode (supplemental
heating is a boiler)
3. by special case
- integration of solar systems
- integration of solid fuel boilers
The following pages show a selec-
tion of these basic hydraulic con-
figurations with the corresponding
basic programming list.
In any case, during commissioning,
assign one of the basic hydraulic
configurations via the menu item
system selection to the “On-site-
system”. Take special care that
the system you select is as near as
possible to system installed on-
site. The location of the sensors is
especially important. Please orient
yourself on the system diagram for
the selected system.
Heating circuit 2 and hot water are recognised by the connected sensor. The relevant menus are hidden if
no sensor is connected.
The systems 2, 3, 4, 5, 8 and 9 were programmed for the equipment type CMF 80/140 and cannot there-
fore be selected for heat pumps with heating meters!
NOTE
46