REMKO Multi-talent Plus User Manual
Page 29
Heating appliance
Designation
Value range
Factory setting
Description
Max T-collector
30.0°C-110.0°C
70.0°C
Setting the maximum collector temperature [sensor 8] (col-
lective supply temperature).
Min T-collector
0.0°C-80.0°C
0.0°C
Setting the minimum collector temperature [sensor 8] (col-
lective supply temperature).
Min T-WE 2
0.0°C-80.0°C
0.0°C
Setting the desired minimum temperature for the WE 2.
Reduces condensate formation in the WE if demand for heat
is low. Shut-off of the WE takes place in all cases at the earli-
est when the minimum temperature+hysteresis set here is
reached.
Hysteresis
2.0K-20.0K
2.0K
Function optimisation of the WE operation at variously
heavy demands on the heating appliance.
The effective switching hysteresis is reduced linearly from
the set hysteresis to the minimum hysteresis in the hysteresis
period following switching on of the burner (= 2.0K).
At low heat transfers the higher hysteresis setting is effective
(short runtimes and frequent synchronising of the burner are
prevented).
For longer burner operation (high heating loads) the hyster-
esis is automatically reduced to 5K (Preheating the heating
appliance to unnecessarily high temperatures is avoided).
Hysteresis period
00 Min.-30 Min.
00 Min.
Setting the hysteresis period.
Sequence change
00 h-800 h
00 h
Setting the desired operating hours for the first WE in
the active sequence, but the active sequence with which
the WE-sequence should switch (time until the sequence
change).
When operating with at least 2 WE, there is the possibility
to switch the WE sequence in accordance with the operating
hours set here.
There is no switch at "00 h".
Clock inhibition
00 Min.-120 Min.
00 Min.
Setting the minimum wait time following switching on of the
WE or for a switching WE, also for switching off of a stage
until switching on of the next stage
(Idle time for the next stage).
At "00 min" the clock inhibition is 10 sec.
Designation
Value range
Factory setting
Description
Sensor
1k/5k sensors
5k sensors
Setting the existing resistance for the connected sensor.
Configuration - continued
Level 4 - SPECIALIST - Description of parameters and settings - continued
29