beautypg.com

REMKO Multi-talent Plus User Manual

Page 29

background image

Heating appliance

Designation

Value range

Factory setting

Description

Max T-collector

30.0°C-110.0°C

70.0°C

Setting the maximum collector temperature [sensor 8] (col-
lective supply temperature).

Min T-collector

0.0°C-80.0°C

0.0°C

Setting the minimum collector temperature [sensor 8] (col-
lective supply temperature).

Min T-WE 2

0.0°C-80.0°C

0.0°C

Setting the desired minimum temperature for the WE 2.

Reduces condensate formation in the WE if demand for heat
is low. Shut-off of the WE takes place in all cases at the earli-
est when the minimum temperature+hysteresis set here is
reached.

Hysteresis

2.0K-20.0K

2.0K

Function optimisation of the WE operation at variously
heavy demands on the heating appliance.

The effective switching hysteresis is reduced linearly from
the set hysteresis to the minimum hysteresis in the hysteresis
period following switching on of the burner (= 2.0K).

At low heat transfers the higher hysteresis setting is effective
(short runtimes and frequent synchronising of the burner are
prevented).

For longer burner operation (high heating loads) the hyster-
esis is automatically reduced to 5K (Preheating the heating
appliance to unnecessarily high temperatures is avoided).

Hysteresis period

00 Min.-30 Min.

00 Min.

Setting the hysteresis period.

Sequence change

00 h-800 h

00 h

Setting the desired operating hours for the first WE in
the active sequence, but the active sequence with which
the WE-sequence should switch (time until the sequence
change).

When operating with at least 2 WE, there is the possibility
to switch the WE sequence in accordance with the operating
hours set here.

There is no switch at "00 h".

Clock inhibition

00 Min.-120 Min.

00 Min.

Setting the minimum wait time following switching on of the
WE or for a switching WE, also for switching off of a stage
until switching on of the next stage
(Idle time for the next stage).

At "00 min" the clock inhibition is 10 sec.

Designation

Value range

Factory setting

Description

Sensor

1k/5k sensors

5k sensors

Setting the existing resistance for the connected sensor.

Configuration - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

29