REMKO Heat Pump Manager
Designation
Value range
Factory setting
Description
WE Dyn up
20-500
350
Setting the value for the connection of all WE-levels
(WE-connection dynamic [K]).
If the cumulative system deviation in Kelvin reaches the
value set here, this effects the connection of all
WE-levels (the smaller the value, the faster the connection).
Values that are too small can lead to overheating or to a
short-term connection of a WE.
WE Dyn down
20-500
20
Setting the value for the shut-off of all WEs
(WE-shut-off dynamic).
If the cumulative system deviation in Kelvin reaches the
value set here, this effects the shut-off of all WEs (the
smaller the value, the faster the shut-off).
Values that are too large can lead to overheating and
triggering of the STB.
Reset time
05-500
30
Setting of the reset time for the I-controller.
Small values lead to fast controller response and can lead to
vibrations.
Adjusting this value can lead to overshooting the controller.
Modgrad on
0 %-100 %
100 %
Setting the modulation depth at which the next WE in the
sequence should be connected.
The connection can take place at the end of the remaining
idle time.
Modgrad off
0 %-100 %
80 %
Setting the modulation depth at which the last WE in the
current sequence should be shut off.
Min modgrad
0 %-100 %
00 %
Setting the modulation depth at which the next WE should
be connected.
The connection of the next WE only takes place if the result-
ing modulation depth for the individual WE following con-
nection exceeds the value set here.
For operation with the maximum number of burners,
Modgrad On must be set to "00%" and Min. Modgrad
must be set to the minimum modulation depth for the WE-
levels.
Modgrad WW
40 %-100 %
100 %
Setting the target modulation depth for the heating appli-
ances in hot water mode.
WE sequence 1
1-2-3-4-5-6-7-8
1-3-2
-4-5-6-7-8
Setting the sequence in which the heating appliances go into
operation at sequence 1.
WE sequence 2
1-2-3-4-5-6-7-8
3-1-2
-4-5-6-7-8
Setting the sequence in which the heating appliances go
into operation at sequence 2 (for two stage WEs, the second
stage is always switched after the first stage).
Cascade - continued
Level 4 - SPECIALIST - Description of parameters and settings - continued