Configuration - continued
Designation
Value range
Factory setting
Description
eBUS supply
On/Off
Off
Activating the eBUS supply in accordance with the con-
nected devices.
System selection
----/01-12
01
With this setting, additional values at the configuration level
can be brought forward (selecting the basic functions).
The display value here is always "00".
• 01 = Basic hydraulics for the functions “Heating and hot
water”, single energy-source mode, 1 supplemental electric
heating, bivalence point -5°C
• 02 = only heating version, single energy-source mode,
2 levels for supplemental electric heating, bivalence point -5°C.
• 03 = only heating version, bivalent mode, boiler + option
for 1 supplemental electric heating, bivalence point -3°C.
• 04 = only heating version, bivalent mode, solid fuel boiler
+ option for supplemental electric
Supplemental heating, bivalence point -3°C.
• 05 = only heating version, single energy-source mode,
1 supplemental electric heating, solar system, bivalence point -5°C.
• 06 = only heating/cooling version, single energy-source
mode, 1 supplemental electric heating, bivalence point -5°C.
• 07 = only heating/cooling version, single energy-source
mode, 1 supplemental electric heating, solar system,
bivalence point -5°C.
• 08 = only heating version, single energy-source mode,
2 levels for supplemental electric heating, solar system,
bivalence point -5°C.
• 09 = only heating version, bivalent mode + option for 1
supplemental electric heating, solar system, bivalence point -3°C.
• 10 = only heating/cooling version, bivalent mode,
bivalence point -3°C
• 11 = heating/cooling version, bivalent mode, solar system,
bivalence point -3°C
• 12 = heating/cooling version, bivalent mode with solid fuel +
option for 1 supplemental electric heating, bivalence point -3°C
There is no change for "----".
Regulator type
00-06
06
Setting the regulation type for the system.
• 00 = No heating appliance (mixer expansion).
• 01 = Single stage WE (switching).
• 02 = Single stage (modulating).
• 03 = Two stage WE (switching).
• 04 = Two individual WE (switching).
• 05 = Multi-level switching (cascade over BUS).
• 06 = Multi-level modulating (cascade over BUS).
WE 1 type
(Output A6
enable or demand
heat pump)
00-09
07
• 00 = Relay has no function.
• 01 = Switch on WE.
• 07 = Switch on heat pump.
• 08 = Switch on cooling 1.
• 09 = Switch on cooling 2.
Level 4 - SPECIALIST - Description of parameters and settings - continued