beautypg.com

Remko heat pump manager – REMKO Multi-talent Plus User Manual

Page 30

background image

REMKO Heat Pump Manager

Designation

Value range

Factory setting

Description

Hyst burner 2

2.0K-20.0K

2.0K

Only for two stage burners or solid material integration.

Setting the hysteresis for the charge pump (solid material
integration) or the 2nd burner

Gradient

On/Off

Off

Activating the gradient process (only for WE 1)

When heat transfer is low, the heating appliance will be shut
off early (e.g. burnout in a pellet boiler).

At "OFF", the shut-off is carried out by the target value and
the hysteresis.

Max reduction

1.0K-20.0K

1.0K

Setting the value for the determination of the earliest shut-
off point (only for WE 1).

The earliest shut-off point is the difference between the
maximum heating appliance temperature Max T-WE
(see specialist cascade) and the value set here.

Dyn shut-off

0.5K/min.-10K/

min.

2.0K/min.

Load dependent, early shut-off of the WE by the the tem-
perature increase gradients [K/min].

If the WE reaches or exceeds the gradient set here, the WE
will be switched off at the earliest dynamic shut-off point
(difference between Max T-WE and Max reduction).

At a low temperature increase, the shut-off point will be in-
creased linearly up to Max T-WE.

WE cooling function

On/Off

Off

Activating the emergency cooling for the WE.

T-WE cold start

30.0°C-120.0°C

95.0°C

Setting the maximum temperature for the heating appliance
(Cooling start temperature).

If emergency cooling for the heating appliance has been ac-
tivated (WE cooling function = ON), the heating circuits will
then be taken with
Max T-supply (see specialist

heating circuit 1/2) into

operation (if emergency cooling is permitted in the heating
circuit), as soon as the temperature set here has been ex-
ceeded by one of the heating appliances.

Emergency cooling is ended if the start temperature T-WE
cold start is undercut by 5K.

Heating appliances - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

30