Remko heat pump manager – REMKO Multi-talent Plus User Manual
Page 30
REMKO Heat Pump Manager
Designation
Value range
Factory setting
Description
Hyst burner 2
2.0K-20.0K
2.0K
Only for two stage burners or solid material integration.
Setting the hysteresis for the charge pump (solid material
integration) or the 2nd burner
Gradient
On/Off
Off
Activating the gradient process (only for WE 1)
When heat transfer is low, the heating appliance will be shut
off early (e.g. burnout in a pellet boiler).
At "OFF", the shut-off is carried out by the target value and
the hysteresis.
Max reduction
1.0K-20.0K
1.0K
Setting the value for the determination of the earliest shut-
off point (only for WE 1).
The earliest shut-off point is the difference between the
maximum heating appliance temperature Max T-WE
(see specialist cascade) and the value set here.
Dyn shut-off
0.5K/min.-10K/
min.
2.0K/min.
Load dependent, early shut-off of the WE by the the tem-
perature increase gradients [K/min].
If the WE reaches or exceeds the gradient set here, the WE
will be switched off at the earliest dynamic shut-off point
(difference between Max T-WE and Max reduction).
At a low temperature increase, the shut-off point will be in-
creased linearly up to Max T-WE.
WE cooling function
On/Off
Off
Activating the emergency cooling for the WE.
T-WE cold start
30.0°C-120.0°C
95.0°C
Setting the maximum temperature for the heating appliance
(Cooling start temperature).
If emergency cooling for the heating appliance has been ac-
tivated (WE cooling function = ON), the heating circuits will
then be taken with
Max T-supply (see specialist
heating circuit 1/2) into
operation (if emergency cooling is permitted in the heating
circuit), as soon as the temperature set here has been ex-
ceeded by one of the heating appliances.
Emergency cooling is ended if the start temperature T-WE
cold start is undercut by 5K.
Heating appliances - continued
Level 4 - SPECIALIST - Description of parameters and settings - continued
30