Cascade
Designation
Value range
Factory setting
Description
WE found
1-3---/x-x---
1-3/x-x
Display of the heating appliance automatically logged by the
BUS with BUS identifier (WE-number).
The displayed "x" indicates that the heating appliance has
answered the BUS.
Output/level
WE 1-WE 8
WE internal
WE 1 level 1 = 50
WE 2 level 1 = 01
WE 3 level 1 = 01
Display of the WE-number and level.
For "---" the level for the WE does not exist.
Following a restart or new configuration, the controller
searches in the BUS systems for heating appliances. In this
period (approx. 1 min.) the output cannot yet be entered
manually.
If a heating appliance answers indicating the output, this
output will automatically be entered in the list.
If a WE answers without indicating the output, the output is
entered in the list with 15KW.
(this value can then be corrected manually).
BUS scan
On/Off
Off
Search for heating appliances in the BUS.
If the displayed configuration is correct, it can be saved with
"OK". All current values are then overwritten.
Min. Mod Cascade
00-100 %
00 %
If the cascade controller calculates a total modulation depth
greater than nil and smaller than Min. Mod Cascade, total
modulation depth will set to the value set here (minimum
modulation depth).
At the same time, clock inhibition will be set to 10 sec.
WW-WE
00-08
00
Water heating by means of collector (00).
The Number of WEs in the cascade which for water heating
are hydraulically decoupled from the cascade (01-08).
System deviation
Display of the current collector system deviation (difference
between target temperature and current temperature
[sensor 08]).
Output target
0-100 %
Display of the currently required total system output
(corresponds with the calculated target value in the
controller).
Remaining idle time
Remainder (min.)
Display of the currently remaining idle time (not until "0"
can the next WE be put into operation).
Max T-WE
50.0°C-110.0°C
72.0°C
Setting the maximum heating appliance temperature.
The WEs shut off/modulate themselves down independently
if they have not reached the temperature set here (protects
the cascade's individual WEs against overheating and
prevents the STB from triggering).
The WEs switch on again if the set temperature is undercut
by 5K.
The temperature set here should be higher than the
maximum collector temperature Max T-collector
(see specialist
heating appliances).