REMKO Multi-talent Plus User Manual
Page 21
Various values are summarised here in order toe enable quick access for customer service.
The input of the code number is necessary for some functions.
The relay test and sensor test are automatically reset after 1 minute!
Sensor test no.
Sensor no.
REMKO
Sensor
designa-
tion
Terminal
layout in the
indoor unit
Description
01
Buffer tank temperature bottom
02
Buffer tank temperature middle (or room temperature Heating circuit 1)
03
Buffer tank temperature top
04
not used
05
F5
X3.16
Supply temperature heating circuit 2 (mixer circuit)
06
F6
X3.15
Hot water temperature top (process water tank)
07
not used
08
F8
X3.14
Collector temperature (collective supply temperature sensor)
09
F9
X3.13
Outdoor temperature
10
not used
11
F11
X3.12
For CMF 80/90/140/150 and CMT 100/150:
Supply temperature heating circuit 1 (direct heating circuit) or
for CMF/CMT 120 and CMF/CMT 160:
Supply temperature heat pump
12
F12
X3.11
Hot water temperature bottom (reference sensor for solar regulation)
13
F13
X3.10
not yet used (solid material WE temperature (PT1000))
14
F14
X3.9
Collector temperature solar system (special control characteristic
(PT 1000))
15
F15
X3.8
Flow meter
16
not used
17
F17
X3.7
Return temperature sensor
Level 4 - SERVICE - Description of parameters and settings
21