Remko heat pump manager – REMKO Multi-talent Plus User Manual
Page 28
REMKO Heat Pump Manager
Designation
Value range
Factory setting
Description
Cooling mode
On/Off
On
Enabling the operating mode cooling and the required settings.
F15 function
00-09
09
Setting the sensor function for sensor 15.
• 00 = Room sensor for heating circuit 2.
If in this position an additional sensor is recognised at the
impulse input (IMP = sensor 17), an FBR at sensors 15 and
17 will be analysed. If sensor 17 is occupied by another
function, an RFB will be analysed at sensor 15.
• 01 = 0-10V input for default of an external collector target
temperature.
• 02 = Light sensor (no function).
• 03 = 0-10V input for default of an external modulation depth.
• 04 = Second sensor for MF - function.
• 05 = Tank 3 (e.g. swimming pool).
• 06 = Sequence/priority switching (e.g. for sequence heat
pumps - conventional heating appliances).
Open contact: WE sequence 1 is active.
Short circuit against ground: WE sequence 2 is active.
• 07 = Locking the heat pumps (e.g. energy supply provider
contact).
Open contact: Heat pumps are enabled.
Short circuit against ground: Heat pumps are locked and the mes-
sage "energy supply provide shut-off" appears in the display.
• 08 = Collective fault heat pumps.
Open contact: Heat pumps are enabled.
Short circuit against ground: Fault in all heat pumps (fault
message, locking of the heat pumps and the corresponding
WE-pumps following termination of the pump run-on).
• 09 = Configuration of the F15-input for a flow volume
sensor (impulse sensor). Important in order to activate the
heating meter function.
E1 function
Signal processing
(Energy supply
provider disable/
enable)
00-03
02
• 00 = No function.
• 01 = Sequence/priority switching (e.g. for sequence heat
pumps – conventional heating appliances).
230V at E1/E2: WE sequence 1 is active.
No phase at E1/E2: WE sequence 2 is active.
• 02 = Locking the heat pumps (e.g. energy supply provider
contact).
230V at E1/E2: Heat pumps are enabled.
No phase at E1/E2: Heat pumps are locked and the message
"WP lock" appears in the display.
• 03 = Collective fault heat pumps.
230V at E1/E2: Heat pumps are enabled.
No phase at E1/E2: Fault in all heat pumps (fault message,
locking of the heat pumps and the corresponding WE-
pumps following termination of the pump run-on).
"Fault heat pump" appears in the display.
E2 function
Signal processing
Collective fault out-
door unit and
flow monitor
00-03
03
Configuration - continued
Level 4 - SPECIALIST - Description of parameters and settings - continued
28