Planning • calculation • units – REMKO PWW Series User Manual

Page 33

background image

33

Planning • Calculation • Units

We reserve the right to make changes to dimensions and design in the interest of technical advances.

Symbol

Unit

Explanation

Q

kW

Heating capacity of air heater

Q = Q

H

+ Q

AL

Q

H

kW

Heating requirement for room to be heated

Q

AL

kW

Heat requirement to heat fresh air to room temperature

Q

AL

= V

AL

· C

PL

· ∆

t

Q

L

kW

Effective heating capacity of air heater with mounted
accessory components

V

m

3

/h

Air volume flow of air heater without mounted
accessory components

V

L

m

3

/h

Effective air volume flow of air heater with mounted
accessory components

V

L

= V

· f

V

V

AL

m

3

/h

Fresh air volume flow

V

AL

= X

· B · L

V

W

l/h

Heating medium volume flow

V

W

=

t

L1

°C

Air inlet temperature at air heater

t

L2

°C

Air outlet temperature at air heater

∆t

°C

Air inlet/outlet temperature difference at air heater

∆t =

t

L2

– t

L1

∆t

W

°C

Heating medium inlet/outlet temperature difference at air heater

∆t

W

= t

W1

– t

W2

∆t

°C

Effective air inlet/outlet temperature difference at air heater
with mounted accessory components

∆t

L

= ∆t · f

L

C

PL

Specific heat capacity of air at constant pressure

ϕ

L

Dry air density

L

m

Length of room to be heated

W

m

Width of room to be heated

H

m

Height of room to be heated

X

1/h

Number of air changes in room to be heated

f

Q

-

Heat output factor

f

Q

= Q

L

/ Q

f

V

-

Air capacity ratio

f

V

= V

L

/ V

f

L

-

Air heating factor

∆P

W

kPa

Heating medium resistance (pressure loss on water-side)

∆P

ST

Pa

Static pressure difference with mounted accessory components

D

-

Pressure difference value with mounted accessory components

kg

m

3

860 · Q

t

W

kWs

———

kg · K

kWs

1 ———

kg · K