REMKO PWW

Care and maintenance

The units are virtually mainte-
nance-free in normal operation.
However, to ensure trouble-free
operation, they should be in-
spected regularly and cleaned if
necessary.

Important precautions to be
taken before carrying out any
maintenance:

The units must be disconnected

from the supply in all poles and
locked to prevent unauthorised
reconnection.

Wait for the fan to stop.

Shut-off the water circuit and

lock to prevent unauthorised
opening.

Allow the fin heat exchanger to

cool down.

Cleaning agents

The units must be cleaned only

dry or with a moist cloth and a
small amount of soap solution if
necessary.

Under no circumstances use

high-pressure cleaners or steam
jet equipment.

Do not use caustic or solvent-

containing cleaning agents.

Only suitable cleaning agents

must be used to remove heavy
fouling.

AttENtiON

It does not suffice to switch off
the unit only via the switch!

NOtE

The fan impeller and alumini-
um fins must not be damaged
or bent.

Cleaning the units

Clean all air inlets and air outlet

fins.

Clean the fan impeller. If ne-

cessary, remove the motor or
protection grille.

Clean the heat exchanger fins

either by blowing out, suction
or with a soft brush.

Remove heavy fouling on the

fan and aluminium fins with a
soap solution.

Repair

Fan replacement

1. Disconnect the electrical con-

nection of the motor.

2. Remove the protection grille

with fan from the housing.

3. Remove the protection grille

from the fan motor.

4. Carefully refit the new fan in

reverse order.

5. Check the fan impeller for

smooth operation and freedom
of movement with respect to
the fan housing.

6. Re-establish the electrical con-

nection of the motor correctly.

Replacement of
fin heat exchanger

1. Disconnect the electrical con-

nection of the unit.

2. Shut-off the water-sided unit

connection.

3. Drain the fin heat exchanger

completely and disconnect the
heating medium connections.

4. Remove any fitted air inlet and

air outlet accessories and re-
move the unit from the bracket
(support).

5. Remove the rear wall (support

plate) together with the fan.

6. Loosen the fin heat exchanger

fastening screws and remove
the heat exchanger towards the
air inlet side.

7. Fit the new heat exchanger and

reassemble the unit in reverse
order including accessories.

8. Re-establish electrical connec-

tions.

Checks after repairs:

The fan impeller must rotate

freely in the fan housing

The distance between the fan

impeller and fan housing must
be the same

The fan motor must rotate in

the direction of the arrow and
connected in correct phase

All screw connections must be

checked for tightness

AttENtiON

After completing all work on
the units, an electrical safety
test must be carried out in
accordance with VDE 0701.

NOtE

Repair and maintenance work
must only be carried out by
authorised specialists.