Exhaust ducting – REMKO CLK 80-RV User Manual
Page 8
8
REMKO CLK 80/170-RV
Example 1
Operation with
extended exhaust
gas ducting
Condensate trap
required
.
Example 2
Operation
without
extended
exhaust gas
ducting.
Max. 1 metre
Example 3
Impermissible
arrangement
More than 1 metre
Max. 1 metre
In order to avoid the combustion
chamber being damaged due
to condensation of moisture
(condensate) in example 3,
make sure that the exhaust gas
ducting is correctly installed
with a condensate trap as shown
in example 1.
Exhaust ducting
■
Fault-free operation
is guaranteed if the exhaust
gas routing is fitted in a rising
arrangement and with a vertical
end pipe
■
The exhaust gas routing should
end at least above the height
of the eaves but ideally above
the height of the ridge, in order
to prevent any counter-pressure
being caused by poor weather
conditions (e.g. wind)
■
The minimum distance of 0.6 m
to combustible parts must not
be infringed
■
Exhaust gas ducting parts
and fastening materials are
available as accessories
It is also possible to operate
the units outside or in open
rooms / halls without exhaust gas
routing.
However, we recommend fitting
a 1m exhaust gas duct with a rain
hood on top (example 2), in order
to exclude the ingress of rainwater
and dirt.
If the units are used for room
heating then the combustion
gases must be routed away,
to the outside if necessary.
■
The exhaust gas routing must
be designed such that the
thermal lift of the exhaust gases
is guaranteed at all times
■
Die The exhaust gas routing
must be designed such that
there can be no counter-
pressure
■
All parts of the exhaust gas
routing must be reliably
fastened. Its diameter must
not be smaller than the outlet
nozzle of the unit.
Notes for implementing the 1st.
BImSchV
Units that are not expected
to be operated for longer than 3
months in the same location are
not subject to any approvals or
monitoring per the 1st. BImSchV.
(§1, section 3)
✔
nOtE
After installing an exhaust
gas system the settings
on the burner should
be adapted to suit the new
conditions.
AttEntiOn
There must be no counter
pressure arising from incorrect
installation of exhaust
gas ducting under any
circumstances.