Setting the pump pressure

The pump pressure should
be adjusted, and checked
if necessary, during burner
commissioning and during every
service.

Adjust the pump pressure
as follows:

1. Remove the stopper

on the measurement nozzle
"P".

2. Fit a suitable oil pressure

manometer here.

3. Open all oil shut-off devices.

4. Switch on the burner.

5. Set the required oil pressure

in accordance with the nozzle
size and the unit capacity.

6. Switch off the burner after

completing the adjustments.

7. Remove the oil pressure

manometer again.
Re-fit stopper incl. seal.

CLK 80-RV

Turning to the left

()

= smaller scale value
larger

pressure behind

the baffle plate
lower

power range

Turning to the right

(+)

= larger scale value
smaller

pressure behind

the baffle plate
upper

power range

CLK 170-RV

Turning to the left

(+)

= larger scale value
smaller

pressure behind

the baffle plate
upper

power range

Turning to the right

()

= smaller scale value
larger

pressure behind

the baffle plate
lower

power range

Adjusting the secondary air
(nozzle fitting adjustment)

Carry out the presetting
of the secondary air as follows:

Set the nozzle fitting 2 to
the desired value with the
adjusting screw 1.

Air flap

3

4

1

2

All values provided are only preliminary settings and must be adapted or calibrated in accordance with the exhaust gas analysis.

The quantity of combustion air
required is adjusted by means
of the adjusting screw 3.
The air flap is set according to the
unit capacity and the further
burner settings.

Adjusting the air flap

Adjust the air flap as follows:

1. Loosen the knurled nut 4.
2. Set the adjusting screw 3

accordingly.

Turn to the right = Less air
Turn to the left = More air
4. After having set the adjusting

screw 3 lock it again with
the knurled knob 4.

Additional notes

If the flame should give off

sooty smoke or break away
with a fully opened air flap,
reduce the pressure behind
the baffle plate with the help
of the secondary air setting

It may also be necessary

to open the air inlet nozzle
further

nOtE

Never let the pump run for
extended periods without any
fuel. Never leave the units for
extended periods with a pump
that has run dry.

AttEntiOn

If the burner should carry out
a fault shut-down once again
after the start phase, then
another reset should be carried
out after a waiting period of 5
minutes has passed.

Further reset procedures
must be prohibited as there
is a danger of deflagration.