Troubleshooting – REMKO CLK 80-RV User Manual

Page 14

background image

14

REMKO CLK 80/170-RV

s

s

s

tensioning the V-belt

1. Remove the two side air intake

grills.

2. Loosen the screws (size 13) [7].

The screw on the opposite side
is not shown.

3. Set the pre-tension

of the V-belt with the (size 17)
nuts [8] and [9].

4. The press-down deflection

depth for the V-belts should
be ca. 10 mm, "a thumb
width".

5. Counter-lock the nuts [8]

and [9] again and then tighten
the two fastening screws [7]
again.

6. Re-fit the two air intake grills.

9

7

8

the unit does not start

1. Check power supply.

400 V/3~N/50Hz.

2. Move the operating switch

to the "I" (Heating) position.

3. The "Operating" indicator

light on the control panel must
illuminate.

4. Check the strapping connector

or the room thermostat plug,
if fitted, is seated properly
and making good contact.

5. Check the setting of the room

thermostat.
The temperature set must
be higher than the current
room temperature.

6. Check whether the safety

temperature limiter (STB) has
tripped.
To do so, remove the protective
cap next to the control panel.

7. Before an STB reset ensure that

the causes have been analysed
and rectified.
The following causes are
possible:

- The units were not able to cool

down because the electrical
connection was interrupted.

- Too high an outlet temperature

due to incorrectly implemented
air routing when operating with
hoses.

- Air inlets or outlets are not free

or are inadequate.

8. Check whether the "Burner

fault" indicator light on
the control panel is illuminated.
If this is the case, then reset
the automatic burner.

troubleshooting

9. Move the operating switch

to the "II" (Ventilate) position.
If the supply air fan now starts
up the fault may well be in the
burner area.

Forced-air burner and power
supply
1. Check the oil filter(s) for

contamination. Replace
contaminated oil filter(s).

2. Check whether the shut-off

cock on the oil filter is open.

3. Check the fuel tank for

sufficient fuel level.

4. Check the heating oil for

paraffin separation.
Possible from 5 °C!

5. Check the oil hoses for damage.
6. Check the safety devices'

capillary tubes and probes for
damage or contamination.

7. Use appropriate means to check

that the temperature monitor
(TW) is functioning properly.

8. Check the forced-air burner for

possible damage to the nozzles,
baffle plate, filter etc.

the supply air fan does not
start
1. Check the fan can move freely.
2. Check the controller fuse in the

switching cabinet.

3. Check whether the motor

protection switch in the
switching cabinet has tripped.

4. Use appropriate means to check

that the temperature controller
(TR) is functioning properly.

nOtE

The press-down deflection
depth for the V-belts should
be ca. 10 mm (a thumb width).

AttEntiOn

Before undertaking any work
on the units, the power
plug must be removed from
the mains socket.