REMKO CLK 80-RV User Manual
Page 13
13
s
s
s
Cleaning the combustion chamber
1. Set the operating
switch to the "0"
position and remove
the power plug from
the mains socket.
2. Remove the burner cladding
[1] after opening the two quick
couplings [2].
3. Loosen the 2 lower fastening
screws on the burner flange [6].
4. Loosen the clamping screw
[7] on the burner flange 6
and withdraw the burner
towards the front.
X
6
7
Additional notes for unit
maintenance
■
All work must be carried out
exclusively by authorised
specialists with the appropriate
equipment.
A log should be created
and kept safely by the operator
■
It is essential that the forced-air
burner is serviced and adjusted
by authorised specialists
1. Check the flange seal
and replace if necessary.
2. Fasten the burner flange to the
unit housing with the four
fastening screws.
Note the "UP"
marking!
3. Tighten the top 2 fastening
screws firmly.
4. Tighten the lower 2 fastening
screws gently and with only
light force so that the burner
flange can still be pulled
together.
5. Slide the flame tube
of the burner into the burner
flange.
Observe dimensions
in the sketch!
6. Clamp the flame tube firmly
into place with the clamping
screw [7] whilst lifting
the burner slightly (3° tilt).
7. Lastly, tighten the bottom 2
fastening screws firmly.
8. Check the fuel filter insert
[3] for leaks and replace
if necessary.
9. Re-fit burner cladding
and fasten with the quick
couplings.
3
4
6
2
1
5
nOtE
The restrictions on exhaust gas
losses per §11 of the ordinance
on small furnace systems
(1st. BImSchV) must
be observed.
5. Withdraw the burner
and carefully set it down beside
the unit.
6. Remove the burner flange [6].
7. Take care not to damage
the flange seals, as far
as is possible.
Damaged flange seals can
result in incorrect air induction.
8. Clean the combustion chamber
through the burner opening
with a vacuum cleaner.
A special boiler cleaning set for
the REMKO industrial vacuum
cleaner is available as an
accessory.
Installation of the burner flange
and the burner
Burner CLK 80-RV: X = 20 mm
Burner CLK 170-RV: X = 30 mm
AttEntiOn
Repair work on the electrical
installation and on the burner
must be performed exclusively
by authorised specialists for
safety reasons.
AttEntiOn
An electrical safety check must
be carried out in accordance
with VDE 0701 after any work
on the units.