If using a spliced terminal connection for longer runs, one module can be
connected to the E-BUS Distribution Module and any additional modules
would be daisy-chained to the fi rst module. For more information, refer
to the E-BUS Distribution Module Technical Guide.
NOTE: Contact Factory for the correct HSSC cable length for
your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.
WARNING!!
Observe Polarity! All
boards must be wired with
GND-to-GND and 24 VAC-
to-24 VAC. Failure to
observe polarity could
result in damage to the
boards.
OE365-23-EBD E-BUS
Distribution Module
GND
-COMM
SHLD
+COMM
INPUT
+COMM
SHLD
-COMM
GND
+VDC
485 DRV
24VAC
GND
PWR
YS102308
REV 1
I2C TO COMM
DIST. BOARD
OUTPUT
Modular Cable
Connect To
VCM-X WSHP or
VCM-X Modular Controller,
HSSC Cable
Connect To E-BUS
Distribution Module
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
COM
Condenser Fan A
ECM Motor
+
Head Pressure Transducers
0 - 667 PSI
(One Per Refrigerant Circuit)
OE370-23-HP2C-C
Two Condenser Head Pressure Module
OPTIONS Dip Switch Setting Not
Required When Connected To
VCM-X Modular, VCM-X WSHP
or SA Controller
+5V
SIG 2
GND
OP
T
IO
N
S
ALARM
ANALOG
STAT
+5V
COMM
GND
SIG 4
GND
BIN 2
R1
R2
GND
RELAYS
ADDRESS
SIG 3
+5V
GND
BIN 1
COM
+5V
SIG 1
R3
R4
Rc
AO1
AO2
PWM1-
PWM1+
PWM2-
PWM2+
Set ADDRESS Dip
Switch 1 to ON for
Water Cooled or to
OFF for Air Cooled.
Currently showing
OFF for Air Cooled.
If Using (2)
Modules, Set
ADDRESS Dip
Switch 2 to OFF for
Address 1 or to ON
for Address 2.
ADDRESS Dip
Switch 4 should
always be set to
ON to make
reversing valve "ON
to Cool / OFF to
Heat". Currently
showing ON.
Set
to OFF if Using (1)
Module. Currently
showing OFF.
Set ADDRESS Dip
Switch 3 to ON to
disable Circuit B
alarms when only
one Condenser is
Used. Currently
showing OFF.
PWR
COM
Condenser Fan B
ECM Motor
+
COM
+
Condenser
Signal B
COM
+
Condenser
Signal A
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
HSSC Cable
24 VAC Transformer
3 VA Minimum
Line Voltage
24 V
A
C
GND
WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.
CONDENSER A ENABLE
R1
HVAC UNIT CONNECTION
R3
CONDENSER B ENABLE
NOTE:
NORMALLY OPEN AND
RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD
ALL RELAY OUTPUTS
ARE
COMM
LED BLINK CODES
LED NAME
STAT
BLINKS QTY. OF SENSORS INSTALLED
LED NAME
ALARM
NO PROBLEMS
0
NO SENSORS DETECTED
1
HIGH HEAD PRESSURE DETECTED
2
LOW HEAD PRESSURE DETECTED
3
WattMaster Label
Rev.: 1H
#LB102081
E-BUS
Connector
E-BUS
Connector
+5V
SIG 1
GND
+5V
SIG 2
GND
+5V
SIG 3
GND
+5V
SIG 4
GND
+24
VAC
GND
BIN 1
BIN 2
COM
HEAD
PRESSURE
TRANSDUCER #1
HEAD
PRESSURE
TRANSDUCER #2
HEAD
PRESSURE
TRANSDUCER #3
HEAD
PRESSURE
TRANSDUCER #4
COMMON
PWM2+
Two Condenser Head Pressure Module
2C
Orion No.:OE370-23-HP
AAON Coil No.:
30310
Circuit A1
Circuit A2
Circuit B1
Circuit B2
www.aaon.com
AO1
AO2
GND
COND. A & B ENABLE
COOL ENABLE
RELA
Y
C
ONT
A
CT
RA
TING
IS
1
A
MP
MAX
@
24
V
A
C
COND. A ENABLE
COND. B ENABLE
COND. A SIGNAL
COND. B SIGNAL
COOL ENABLE
COOL ENABLE
PWM1-
PWM1+
PWM2-
COND. FAN A
COND. FAN B
COND. FAN A
COND. FAN B
GND
R1
R2
R3
R4
RC
RELAY COMMON
WARNING: Be sure all controllers and modules are
powered down before connecting or
disconnecting HSSC cables.
VCM-X Controller to Two Condenser Head Pressure Module Wiring
Figure 4, cont.: VCM-X WSHP Controller to Two Condenser Head Pressure Module Wiring Diagram