Two condenser head pressure module, Appendix for version 1.04 and earlier – Orion System Two Condenser Head Pressure Module User Manual
Page 23

Technical Guide
Two Condenser Head Pressure Module
23
Appendix for Version 1.04 and Earlier
Table 11: ADDRESS Dip Switch Refrigerant and Condenser Type Settings for Stand-Alone Operation
ADDRESS Dip Switch 1 & 2 Settings
Switch 1
Switch 2
Default SP
Description of Default Head Pressure Setpoint
OFF
OFF
340
Air Cooled Condenser using R410-A Refrigerant
OFF
ON
200
Air Cooled Condenser using R22 Refrigerant
ON
OFF
235
Water Cooled Condenser using R410-A Refrigerant
ON
ON
145
Water Cooled Condenser using R22 Refrigerant
Switch 1 determines Air or Water Cooled Condenser
Switch 2 determines R410-A or R22 refrigerant
NOTE: R22 refrigerant can only be used with the Two Condenser Head Pressure Module versions 1.01 through 1.04.
You must cycle power after setting Dip Switch values.