Two condenser head pressure module, Sequence of operation – Orion System Two Condenser Head Pressure Module User Manual
Page 14

Two Condenser Head Pressure Module
Technical Guide
14
ADDRESS Dip Switch 3 Settings
Switch Description
OFF
Enable Circuit B Alarm
ON
Disable Circuit B Alarm when only one condenser is
used.
Table 5: ADDRESS Dip Switch 3 Settings
ADDRESS Dip Switch 4 Settings
Switch Description
ON
Reversing Valve On to Cool / Off to Heat
OFF
Reversing Valve On to Heat / Off to Cool
This Dip Switch should be set to ON for AAON Coil operations.
Table 6: ADDRESS Dip Switch 4 Settings for Reversing Valve
Sequence of Operation
Revised 11/2/11
ADDRESS Dip Switch 2 Settings
Switch Description
OFF
Address 1 if Using (2) Head Pressure Modules
(Set to OFF if using only (1) Head Pressure Module)
ON
Address 2 if Using (2) Head Pressure Modules
Table 4: ADDRESS Dip Switch Address Settings When Connected to VCM-X / SA