Two condenser head pressure module, Troubleshooting, Technical guide – Orion System Two Condenser Head Pressure Module User Manual
Page 17: Pressure transducer troubleshooting
Technical Guide
Two Condenser Head Pressure Module
17
Troubleshooting
Table 7: Two Condenser Head Pressure Module
Transducer Chart
Pressure Transducer Troubleshooting
If you suspect there is a problem with the Module related to pressure
transducer measurements, reference Table 7 below.
Pressure Sensor Chart
Voltage Pressure Voltage Pressure
0.5
0
2.6
350
0.6
17
2.7
367
0.7
33
2.8
384
0.8 50
2.9
400
0.9 67
3.0
417
1.0 83
3.1
434
1.1
100
3.2
450
1.2
117
3.3
467
1.3
133
3.4
484
1.4
150
3.5
500
1.5
167
3.6
517
1.6
183
3.7
534
1.7
200
3.8
550
1.8
217
3.9
567
1.9
233
4.0
584
2.0
250
4.1
600
2.1
267
4.2
617
2.2
283
4.3
634
2.3
300
4.4
650
2.4
317
4.5
667
2.5
334
This manual is related to the following products: