Two condenser head pressure module, Appendix for version 1.04 and earlier, Technical guide 22 – Orion System Two Condenser Head Pressure Module User Manual
Page 22

Two Condenser Head Pressure Module
Technical Guide
22
Appendix for Version 1.04 and Earlier
Table 10: OPTIONS Dip Switch/Head Pressure Setpoint Settings for Stand-Alone Operation
OPTIONS Dip
Switch Settings
Head Pressure Setpoint
Air Cooled Condenser
Water Cooled Condenser
Binary Value
R410-A
R22
R410-A
R22
0
340 (DEFAULT)
200 (DEFAULT)
235 (DEFAULT)
145 (DEFAULT)
1
260
160
210
110
2
270
170
220
120
3
280
180
230
130
4
290
190
240
140
5
300
200
250
150
6
310
210
260
160
7
320
220
270
170
8
330
230
280
180
9
340
240
290
190
10
350
250
300
200
11
360
260
310
210
12
370
270
320
220
13
380
280
330
230
14
390
290
340
240
15
400
300
350
250
NOTE: R22 refrigerant can only be used with the Two Condenser Head Pressure Module versions 1.01 through 1.04.
You must cycle power after setting Dip Switch values.