SECTION 5.0: DIAGNOSTICS

5.1 DIAGNOSTICS

The ONICON System-10 BTU Meter uses a microprocessor

to calculate energy. Factory programmed settings provide

rate and total values in accordance with the customer’s

application data. Refer to the BTU meter certificate of

calibration for a complete listing of factory settings. These

settings may be reviewed and changed with assistance from

ONICON.

The System-10 BTU Meter is also equipped with diagnostic

indicator lights and self diagnostic test signals that confirm

the operation of the microprocessor and its input circuitry.

Please contact ONICON if any of the diagnostic lights or

test signals listed below indicates a potential problem with

the operation of the BTU meter.

5.1.1 Diagnostic Lights

Low Voltage Power Supply

Located on the power supply board inside the System-10 BTU Meter (refer to A-15),

is a single LEDs that will illuminat when +15 VDC is present.

Liquid Flow

Located in the center of the motherboard (refer to A-12) next to terminal block T5, the

LED will flash at a rate that is proportional to the liquid flow rate for frequency flow

signals. For 4 - 20 mA signals, the light will stay lit whenever the output is greater than

4 mA. An unlit LED indicates no flow signal.

5.1.2 Flow Test Signals

Flow Test

Located in the center of the motherboard (Refer to A-12) immediately above the power

supply board is a three position slide switch used to test the flow input. When the switch

is in the top position, the BTU meter input is connected to the flow meter. When the

switch is in the middle position, the BTU meter input is connected to two test terminals

used to apply a variable frequency to simulate flow. When the switch is in the bottom

position, the BTU meter input is connected to a 50/60 Hz signal that simulates a fixed flow

rate. Refer to the BTU meter certificate of calibration to determine the correct display

reading when operating in the 50/60 Hz test mode.

5.1.3 Temperature Test Signals

Temperature Test

As you are facing the component side of the BTU computer board, the temperature test

pushbutton is along the top edge of the board just to the left of the flat ribbon cable. It is

labeled TEMP TEST. When pressed, a fixed voltage will be applied to each temperature

sensor input. Both the supply and return temperature menu pages will display a

temperature between 98° F to 102° F (36.6° C to 38.9° C). This test confirms the operation

of the BTU computer board input circuitry for temperature measurement.