3.3.4 Isolated Analog Output(s) (Optional):
The System-10 can be configured to provide up to four isolated analog outputs of the
following five parameters: supply temperature, return temperature, flow rate, BTU rate and
delta temperature. The output type, 4-20 mA, 0-10 VDC or 5 VDC is field configurable. The
selected outputs and associated scaling are configured at the factory. See the calibration sheet
or label, located on the inside cover, for analog output configuration information.
Please Note: If System-10 is ordered with a flow meter capable of producing an analog
output, flow rate analog output will be available at Terminal T4 from flow meter.