Nortec Modbus User Manual

Page 39

background image

ForceReset

Resets the

controller

and restarts

in standby.

40007 Holding

Register integer 0,255

-

Write

Write 255 to this register

to reset the control. The

controller will reset,

restart, and remain in

standby mode. After

completion:

- WasReset (40002 )will

read 255 (reset has

occurred)

- HumEnable (40003) will

read 0 (unit is disabled)

TimeWindo

w

Sets the

permissible

window for

modbus

data to be

written.

40208 Holding

Register Integer

0 -

255

-

Write

Each integer is a multiple

of 200mS. Maximum time

of 51 secs occurs when

the register reads 255.

A value of 0 disables the

timeout, but can only be

written with HumEnable

(40003) is set to 0

(disabled).

Current

Displays

current

draw in

Amps.

30104

Input

Register Integer

0 -

12495

Amps

Read

Each bit represents

0.0024 Amps, therefore

1 Amp = 416 bits.

The Amp value does not

clear when security loop

is open and the

demand is 0. The last

detected value remains

in the register.

SteamOutp

ut

Displays the

steam

output in

either

Metric of

Imperial

units.

30105

Input

Register Integer 0 - 300

lbs/hr

kg/hr

Read

Units are defined in

Units (register 40204).

Unit includes decimal

point as integer value.

Example:

17 = 1.7 (kg/hr or

lbs/hr)

This variable does not

clear when the security

loop is open and the

demand 0. The last

detected value remains

in the register.

RunHrs

Run hour

Counter

30106

Input

Register Integer

0 -

24000

min

Read

Steam production hours

since last reset. Max

possible 2000 hrs of

operation. Each integer

is a multiple of 5

minutes. Example:

1 = 5minutes

12 = 60 minutes (1 hr)

Firmware

Displays

unit

firmware

version.

30113

Input

Register Integer

-

-

Read Example: 352 = Version

3.52

36

|Modbus Installation