Nortec Modbus User Manual
Page 39
ForceReset
Resets the
controller
and restarts
in standby.
40007 Holding
Register integer 0,255
-
Write
Write 255 to this register
to reset the control. The
controller will reset,
restart, and remain in
standby mode. After
completion:
- WasReset (40002 )will
read 255 (reset has
occurred)
- HumEnable (40003) will
read 0 (unit is disabled)
TimeWindo
w
Sets the
permissible
window for
modbus
data to be
written.
40208 Holding
Register Integer
0 -
255
-
Write
Each integer is a multiple
of 200mS. Maximum time
of 51 secs occurs when
the register reads 255.
A value of 0 disables the
timeout, but can only be
written with HumEnable
(40003) is set to 0
(disabled).
Current
Displays
current
draw in
Amps.
30104
Input
Register Integer
0 -
12495
Amps
Read
Each bit represents
0.0024 Amps, therefore
1 Amp = 416 bits.
The Amp value does not
clear when security loop
is open and the
demand is 0. The last
detected value remains
in the register.
SteamOutp
ut
Displays the
steam
output in
either
Metric of
Imperial
units.
30105
Input
Register Integer 0 - 300
lbs/hr
kg/hr
Read
Units are defined in
Units (register 40204).
Unit includes decimal
point as integer value.
Example:
17 = 1.7 (kg/hr or
lbs/hr)
This variable does not
clear when the security
loop is open and the
demand 0. The last
detected value remains
in the register.
RunHrs
Run hour
Counter
30106
Input
Register Integer
0 -
24000
min
Read
Steam production hours
since last reset. Max
possible 2000 hrs of
operation. Each integer
is a multiple of 5
minutes. Example:
1 = 5minutes
12 = 60 minutes (1 hr)
Firmware
Displays
unit
firmware
version.
30113
Input
Register Integer
-
-
Read Example: 352 = Version
3.52
36