Nortec Modbus User Manual

Page 22

background image

Set2Cyl2

Writes the

desired space

setpoint for

control

channel 2 for

cylinder 2

41010

Holding

Register Integer 30-95

%

Write

Use only with NHTC-150

and NHTC-200 models

when sending RH value to

RHDem2 with dual

channel control enabled

and cylinders are in

independent operation

mode

DisableCyl1

Remotely

disable steam

production for

cylinder 1

40262

Holding

Register Integer

0 or

255

-

Write 0 = Normal operation

255 = Disabled

DisableCyl2

Remotely

disable steam

production for

cylinder 2

41262

Holding

Register Integer

0 or

255

-

Write

Used only for NHTC-150

and NHTC-200 models.

Both cylinder 1 and 2

must be disabled to

completely disable

humidifier.

0 = Normal operation

255 = Disabled

NetSensor

Switches

between hard

wired or

network

control signal

40226

Holding

Register Integer 0 or 1

-

Write

1= Network sensor or

demand

0 = Wired sensor or wired

demand

Ch1DemCyl1

Displays

channel 1

demand for

cylinder 1

30348

Input

Register Integer

0 -

100

%

Read

Displays channel 1

demand as a percentage

of cylinder capacity for

cylinder 1

Ch1DemCyl2

Displays

channel 1

demand for

cylinder 2

31348

Input

Register Integer

0 -

100

%

Read

Displays channel 1

demand / output as a

percentage of cylinder

capacity for cylinder 2

(NHTC-150 and NHTC-

200 models only)

Ch2DemCyl1

Displays

channel 2

demand for

cylinder 1

30349

Input

Register Integer

0 -

100

%

Read

Displays channel 2

demand as a percentage

of cylinder capacity for

cylinder 1

Ch2DemCyl2

Displays

channel 2

demand for

cylinder 2

31349

Input

Register Integer

0 -

100

%

Read

Displays channel 2

demand / output as a

percentage of cylinder

capacity for cylinder 2

(NHTC-150 and NHTC-

200 models only)

Fault Warning

Reads fault

status

30301

Input

Register Integer

0 or

255

-

Read 0 = No Fault

255 = Fault Warning

Service Warning

Reads service

warning

status

30300

Input

Register Integer

0 or

255

-

Read 0 = No Service Warning

255 = Service Warning

Unit Status

Reads unit

status

30312

Input

Register Integer

0 or

255

-

Read

0 = Idle / Standby

255 = Active /

Humidifying

Cyl1OpTime

Reads

operating

time for

cylinder 1

30213

Input

Register Integer

0 -

65535

5

min Read

Reads operating time for

cylinder 1. Each number

is equivalent to 5 minutes

of operation. Time in

hours = (Value x 5)/60

Modbus Installation | 19