Nortec Modbus User Manual
Page 38
Baud
Sets the
Modbus
baud rate
40202 Holding
Register Integer
0,1,2
-
Write
Changes to this variable
do not take effect until
the humidifier has been
power cycled.
0 = 4800 bps
1 = 9600 bps (Default)
2 = 19200 bps
Parity
Set Modbus
Parity
40203 Holding
Register Integer
0,1,2
-
Write
Changes to this variable
do not take effect until
the humidifier has been
power cycled.
0 = No parity
1 = Even parity (Default)
2 = Odd parity
RunHrReset
Allows the
run hour
counter to
be reset to
0, typically
used
following
maintenanc
e.
40006 Holding
Register Integer 0, 255
-
Write
Requires that HumEnable
is set to 0 (disabled) first
or ILLEGAL DATA error will
occur.
255 = Reset the run time
hours (reported in
RunHrs) to 0.
Value reverts to 0 after
operation is complete.
Units
Switches
between
imperial
(lbs/hr) and
metric
(kg/hr)
units.
40204 Holding
Register Integer
0,1
-
Write
0 = Imperial (lbs/hr)
1 = Metric (kg/hr)
Changes values reported
in Model (40205) and
SteamOutput (30105).
Model
Allows
writing of
humidifier
capacity to
match
model.
40205 Holding
Register Integer 0 - 30
-
Write
Value represents
maximum unit capacity, in
lbs/hr, at 100% Fill Off
Amps.
Value cannot be written
while HumEnable = 255
(operational).
The MES-005 would be
written as 5. (Default = 8)
Voltage
Unit voltage 40206 Holding
Register Integer
1 to
10
-
Write
Reads the jumper (J1 thru
6) pin settings and
reports the voltage:
0: 110-120V (J6 installed)
1: 208V (J6 installed)
2: 220-240V (J5 installed)
3: 230V
4: 277V (J4 installed)
5: 347V
6: 380V (J3 installed)
7: 400V (J3 installed)
8: 415V (J3 installed)
9: 440-480V (J2 installed,
Default)
10: 550-600V (J1
installed)
Phase
Unit voltage
phases
40207 Holding
Register Integer
0,1,2
-
Write
0 = Single phase
1 = 3 phase (Default)
2 = 3 phase (6 electrode)
Modbus Installation | 35