Nortec Modbus User Manual

Page 35

background image

NetSensor

Switches

between hard

wired or

network

control signal

40002

Holding

Register

Integer 0 or 1

-

Write

0 = Wired Analog

Sensor/Demand

1 = Modbus/Remote

Sensor/Demand

Stage1Dem

Indicates

output from

humidifier

stage 1

30025

Input

Register

Integer 0 or 1

-

Read 0 = Inactive

1 = Active

Stage2Dem

Indicates

output from

humidifier

stage 2

30026

Input

Register

Integer 0 or 1

-

Read 0 = Inactive

1 = Active

Stage3Dem

Indicates

output from

humidifier

stage 3

30027

Input

Register

Integer 0 or 1

-

Read 0 = Inactive

1 = Active

Warning

Indicates

warning

status

30015

Input

Register

Integer 0 or 1

-

Read 0 = No warning

1 = Warning

Service

Indicates

maintenance

requirement

30016

Input

Register

Integer 0 or 1

-

Read

0 = No service

required

1 = Service required

Fault

Indicates fault

status

30017

Input

Register

Integer 0 or 1

-

Read 0 = No error

1 = Error(s) detected

Cleaning

Indicates

automatic

stage cleaning

cycle status

30018

Input

Register

Integer 0 or 1

-

Read 0 = Inactive

1 = Active

TankDrain

Indicates

automatic

tank drain

status

30019

Input

Register

Integer 0 or 1

-

Read 0 = Inactive

1 = Active

PumpRunHr

Displays

pump

operational

hours

30100

Input

Register

Integer

0 -

65535

10

min

Read 1Bit = 10min (max.

10’922h)

UVRunHr

Displays UV

lamp

operational

hours

30101

Input

Register

Integer

0 -

65535

10

min

Read 1Bit = 10min (max.

10’922h)

ServTime

Displays unit

operational

hours

30102

Input

Register

Integer

0 -

65535

10

min

Read 1Bit = 10min (max.

10’922h)

Security

Indicates

security loop

status

(humidifier

terminals 1

and 2)

30200

Input

Register

Integer 0 or 1

-

Read

Humidifier will only

operate when

security loop is

closed.

0 = Off

1 = On

TankLevel

Max Level

Sensor

30202

Input

Register

Integer 0 or 1

-

Read

0 = Tank below full

level

1 = Tank full

System

Ready

Indicates

when the

humidifier is

ready to

commence

stages

30013

Input

Register

Integer 0 or 1

-

Read

0 = System busy

(cleaning or draining)

1 = System ready to

Humidify

32

|Modbus Installation