Nortec Modbus User Manual
Page 35
NetSensor
Switches
between hard
wired or
network
control signal
40002
Holding
Register
Integer 0 or 1
-
Write
0 = Wired Analog
Sensor/Demand
1 = Modbus/Remote
Sensor/Demand
Stage1Dem
Indicates
output from
humidifier
stage 1
30025
Input
Register
Integer 0 or 1
-
Read 0 = Inactive
1 = Active
Stage2Dem
Indicates
output from
humidifier
stage 2
30026
Input
Register
Integer 0 or 1
-
Read 0 = Inactive
1 = Active
Stage3Dem
Indicates
output from
humidifier
stage 3
30027
Input
Register
Integer 0 or 1
-
Read 0 = Inactive
1 = Active
Warning
Indicates
warning
status
30015
Input
Register
Integer 0 or 1
-
Read 0 = No warning
1 = Warning
Service
Indicates
maintenance
requirement
30016
Input
Register
Integer 0 or 1
-
Read
0 = No service
required
1 = Service required
Fault
Indicates fault
status
30017
Input
Register
Integer 0 or 1
-
Read 0 = No error
1 = Error(s) detected
Cleaning
Indicates
automatic
stage cleaning
cycle status
30018
Input
Register
Integer 0 or 1
-
Read 0 = Inactive
1 = Active
TankDrain
Indicates
automatic
tank drain
status
30019
Input
Register
Integer 0 or 1
-
Read 0 = Inactive
1 = Active
PumpRunHr
Displays
pump
operational
hours
30100
Input
Register
Integer
0 -
65535
10
min
Read 1Bit = 10min (max.
10’922h)
UVRunHr
Displays UV
lamp
operational
hours
30101
Input
Register
Integer
0 -
65535
10
min
Read 1Bit = 10min (max.
10’922h)
ServTime
Displays unit
operational
hours
30102
Input
Register
Integer
0 -
65535
10
min
Read 1Bit = 10min (max.
10’922h)
Security
Indicates
security loop
status
(humidifier
terminals 1
and 2)
30200
Input
Register
Integer 0 or 1
-
Read
Humidifier will only
operate when
security loop is
closed.
0 = Off
1 = On
TankLevel
Max Level
Sensor
30202
Input
Register
Integer 0 or 1
-
Read
0 = Tank below full
level
1 = Tank full
System
Ready
Indicates
when the
humidifier is
ready to
commence
stages
30013
Input
Register
Integer 0 or 1
-
Read
0 = System busy
(cleaning or draining)
1 = System ready to
Humidify
32
|Modbus Installation