Modbus address, Control signal setting – Nortec Modbus User Manual

Page 24

background image

GSTC Gas Fired Steam Humidifiers

After wiring connections have been completed, the humidifier needs to be setup to operate and

communicate through the Modbus interface.

Modbus Address

The default Modbus address for a GSTC is 1. If multiple units were included on an order, the

addresses of individual units may vary.

To view or change the unit number:

1 Press the Menu key to access the menu.
2 When prompted for a password, enter 0335 using the arrow keys. Press Set to confirm.
3 Select the Control Settings menu and press the Set key.
4 Select the Modbus Parameters menu and press the Set key.
5 Select the Address setting and press Set to modify. Enter a value between 1 and 127

inclusive as desired and press Set to confirm the solution. It is recommended to leave the
parity and timeout settings to their factory defaults (None1 and 300 respectively) unless
communication problems occur.

6 Press Esc repeatedly until you return to the home screen.

This procedure is summarized below:

Menu > 0335 > Control Settings > Modbus Parameters >

Parity: None1

Addr: 1 (Default, 1 – 127 acceptable)

Timeout: 300 seconds (Default, 5 – 600 acceptable)

Control Signal Setting

By default the humidifier is configured operate on a hardwired control signal supplied through

the unit terminal strip. This can be changed to allow the humidifier to function entirely through

its Modbus interface.

Modbus Installation | 21