beautypg.com

Nortec Modbus User Manual

Page 17

background image

Fan_

Activate_B

Indicates if air

handle or furnace

is activated for

cylinder B

30019

Input

Register Integer

0 or 1

-

Read

0 = Not Activated

1 = Activated

Do_Fault_

A

Reads the status

of a fault on the

unit

30025

Input

Register Integer

0 or 1

-

Read

0 = No Fault

1 = Fault

Do_

Service_A

Reads the status

of a service

request on the unit

30024

Input

Register Integer

0 or 1

-

Read

0 = No Service

Required

1 = Service Required

Humidifier

_Status_A

Reads the status

of the unit for

cylinder A

30003

Input

Register Integer

0 - 9

-

Read

0 = Humidifying

1 = Idle

2 = Idle Drain

3 = Keepwarm

4 = Filling

5 = Draining

6 = Disabled

7 = Safety Loop

8 = Warning

9 = Fault

Humidifier

_Status_B

Reads the status

of the unit for

cylinder A

30026

Input

Register Integer

0 - 9

-

Read

0 = Humidifying

1 = Idle

2 = Idle Drain

3 = Keepwarm

4 = Filling

5 = Draining

6 = Disabled

7 = Safety Loop

8 = Warning

9 = Fault

System_

Demand_A

Reads the demand

for cylinder A

30006

Input

Register Integer 0 – 100

%

Read

Demand Mode:

Summation of Input_A1

and Input_A2

RH Mode:

PID calculation

System_

Demand_

B

Reads the demand

for cylinder A

30016

Input

Register Integer 0 – 100

%

Read

Demand Mode:

Summation of Input_B1

and Input_B2

RH Mode:

PID calculation

Safety_

Loop_A

Reads the status

of the safety loop

for cylinder A

30007

Input

Register Integer

0 or 1

-

Read

0 = Open

1 = Closed

Safety_

Loop_B

Reads the status

of the safety loop

for cylinder B

30017

Input

Register Integer

0 or 1

-

Read

0 = Open

1 = Closed

Run_Time

_A

Reads operating

time for cylinder A

30010

Input

Register Integer 0 - 5000 Hrs

Read

Displays the total time

cylinder A has been

running since last reset

Run_Time

_B

Reads operating

time for cylinder B

30020

Input

Register Integer 0 - 5000 Hrs

Read

Displays the total time

cylinder B has been

running since last reset

Weighted_

Hours_A

Reads the

weighted time for

cylinder A

30011

Input

Register Integer 0 - 5000 Hrs

Read

An equated run time

based on Run_Time_A x

System_Demand_A

Weighted_

Hours_B

Reads the

weighted time for

cylinder B

30021

Input

Register Integer 0 - 5000 Hrs

Read

An equated run time

based on Run_Time_A x

System_Demand_A

14

|Modbus Installation