Nortec Modbus User Manual
Page 17
Fan_
Activate_B
Indicates if air
handle or furnace
is activated for
cylinder B
30019
Input
Register Integer
0 or 1
-
Read
0 = Not Activated
1 = Activated
Do_Fault_
A
Reads the status
of a fault on the
unit
30025
Input
Register Integer
0 or 1
-
Read
0 = No Fault
1 = Fault
Do_
Service_A
Reads the status
of a service
request on the unit
30024
Input
Register Integer
0 or 1
-
Read
0 = No Service
Required
1 = Service Required
Humidifier
_Status_A
Reads the status
of the unit for
cylinder A
30003
Input
Register Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
Humidifier
_Status_B
Reads the status
of the unit for
cylinder A
30026
Input
Register Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
System_
Demand_A
Reads the demand
for cylinder A
30006
Input
Register Integer 0 – 100
%
Read
Demand Mode:
Summation of Input_A1
and Input_A2
RH Mode:
PID calculation
System_
Demand_
B
Reads the demand
for cylinder A
30016
Input
Register Integer 0 – 100
%
Read
Demand Mode:
Summation of Input_B1
and Input_B2
RH Mode:
PID calculation
Safety_
Loop_A
Reads the status
of the safety loop
for cylinder A
30007
Input
Register Integer
0 or 1
-
Read
0 = Open
1 = Closed
Safety_
Loop_B
Reads the status
of the safety loop
for cylinder B
30017
Input
Register Integer
0 or 1
-
Read
0 = Open
1 = Closed
Run_Time
_A
Reads operating
time for cylinder A
30010
Input
Register Integer 0 - 5000 Hrs
Read
Displays the total time
cylinder A has been
running since last reset
Run_Time
_B
Reads operating
time for cylinder B
30020
Input
Register Integer 0 - 5000 Hrs
Read
Displays the total time
cylinder B has been
running since last reset
Weighted_
Hours_A
Reads the
weighted time for
cylinder A
30011
Input
Register Integer 0 - 5000 Hrs
Read
An equated run time
based on Run_Time_A x
System_Demand_A
Weighted_
Hours_B
Reads the
weighted time for
cylinder B
30021
Input
Register Integer 0 - 5000 Hrs
Read
An equated run time
based on Run_Time_A x
System_Demand_A
14
|Modbus Installation