Nortec LINKS 2 NHRS User Manual
Page 27

Installation | 23
Table 5: Humidifier Variable Addresses - CONTINUED
BACnet
Lonworks
N2
Variables
Data
Type
Object
ID
SNVT
Type
SNVT
Index
Data Type
Address
Unit 8 Variable Name
nviRHDem_8
AV 106
SNVT_lev_percent
211
Analog Output
106
nviSet_8
AV 107
SNVT_lev_percent
212
Analog Output
107
nviCapLimit_8
AV 108
SNVT_lev_percent
213
Analog Output
108
Not Used
AV 109
SNVT_lev_percent
214
Analog Output
109
Not Used
AV 110
SNVT_lev_percent
215
Analog Output
110
nvoRHDem_8
AV 111
SNVT_lev_percent
216
Analog Input
111
nvoSet_8
AV 112
SNVT_lev_percent
217
Analog Input
112
nvoCapLimit_8
AV 113
SNVT_time_hour
218
Analog Input
113
nvoSysDemand_8
AV 114
SNVT_time_hour
219
Analog Input
114
nvoHourOpt_8
AV 115
SNVT_time_hour
220
Analog Input
115
nvoSmallHrs_8
AV 116
SNVT_time_hour
221
Analog Input
116
nvoLargeHrs_8
AV 117
SNVT_lev_percent
222
Analog Input
117
Not Used
AV 118
SNVT_lev_percent
223
Analog Input
118
Not Used
AV 119
SNVT_lev_percent
224
Analog Input
119
Not Used
AV 120
SNVT_lev_percent
225
Analog Input
120
nviNetSensor_8
BV 106
SNVT_switch
226
Digital Output
106
Not Used
BV 107
SNVT_switch
227
Digital Output
107
Not Used
BV 108
SNVT_switch
228
Digital Output
108
nvoNetSensor_8
BV 109
SNVT_switch
229
Digital Input
109
nvoStatus_8
BV 110
SNVT_switch
230
Digital Input
110
nvoService_8
BV 111
SNVT_switch
231
Digital Input
111
nvoFault_8
BV 112
SNVT_switch
232
Digital Input
112
nvoInputType_8
BV 113
SNVT_switch
233
Digital Input
113
nvoConnection_8
BV 114
SNVT_switch
234
Digital Input
114
Not Used
BV 115
SNVT_switch
235
Digital Input
115
Not Used
BV 116
SNVT_switch
236
Digital Input
116
Not Used
BV 117
SNVT_switch
237
Digital Input
117
Not Used
BV 118
SNVT_switch
238
Digital Input
118
Not Used
BV 119
SNVT_switch
239
Digital Input
119
Not Used
BV 120
SNVT_switch
240
Digital Input
120