Nortec LINKS 2 NHRS User Manual
Page 23
Installation | 19
Table 5: Humidifier Variable Addresses - CONTINUED
BACnet
LonWorks
N2
Variables
Data
Type
Object
ID
SNVT Type
SNVT
Index
Data Type
Address
Unit 4 Variable Name
nviRHDem_4
AV 46
SNVT_lev_percent
91
Analog Output
46
nviSet_4
AV 47
SNVT_lev_percent
92
Analog Output
47
nviCapLimit_4
AV 48
SNVT_lev_percent
93
Analog Output
48
Not Used
AV 49
SNVT_lev_percent
94
Analog Output
49
Not Used
AV 50
SNVT_lev_percent
95
Analog Output
50
nvoRHDem_4
AV 51
SNVT_lev_percent
96
Analog Input
51
nvoSet_4
AV 52
SNVT_lev_percent
97
Analog Input
52
nvoCapLimit_4
AV 53
SNVT_time_hour
98
Analog Input
53
nvoSysDemand_4
AV 54
SNVT_time_hour
99
Analog Input
54
nvoHourOpt_4
AV 55
SNVT_time_hour
100
Analog Input
55
nvoSmallHrs_4
AV 56
SNVT_time_hour
101
Analog Input
56
nvoLargeHrs_4
AV 57
SNVT_lev_percent
102
Analog Input
57
Not Used
AV 58
SNVT_lev_percent
103
Analog Input
58
Not Used
AV 59
SNVT_lev_percent
104
Analog Input
59
Not Used
AV 60
SNVT_lev_percent
105
Analog Input
60
nviNetSensor_4
BV 46
SNVT_switch
106
Digital Output
46
Not Used
BV 47
SNVT_switch
107
Digital Output
47
Not Used
BV 48
SNVT_switch
108
Digital Output
48
nvoNetSensor_4
BV 49
SNVT_switch
109
Digital Input
49
nvoStatus_4
BV 50
SNVT_switch
110
Digital Input
50
nvoService_4
BV 51
SNVT_switch
111
Digital Input
51
nvoFault_4
BV 52
SNVT_switch
112
Digital Input
52
nvoInputType_4
BV 53
SNVT_switch
113
Digital Input
53
nvoConnection_4
BV 54
SNVT_switch
114
Digital Input
54
Not Used
BV 55
SNVT_switch
115
Digital Input
55
Not Used
BV 56
SNVT_switch
116
Digital Input
56
Not Used
BV 57
SNVT_switch
117
Digital Input
57
Not Used
BV 58
SNVT_switch
118
Digital Input
58
Not Used
BV 59
SNVT_switch
119
Digital Input
59
Not Used
BV 60
SNVT_switch
120
Digital Input
60