Nortec LINKS 2 NHRS User Manual
Page 26
22 | Installation
Table 5: Humidifier Variable Addresses - CONTINUED
BACnet
LonWorks
N2
Variables
Data
Type
Object
ID
SNVT Type
SNVT
Index
Data Type
Address
Unit 7 Variable Name
nviRHDem_7
AV 91
SNVT_lev_percent
181
Analog Output
91
nviSet_7
AV 92
SNVT_lev_percent
182
Analog Output
92
nviCapLimit_7
AV 93
SNVT_lev_percent
183
Analog Output
93
Not Used
AV 94
SNVT_lev_percent
184
Analog Output
94
Not Used
AV 95
SNVT_lev_percent
185
Analog Output
95
nvoRHDem_7
AV 96
SNVT_lev_percent
186
Analog Input
96
nvoSet_7
AV 97
SNVT_lev_percent
187
Analog Input
97
nvoCapLimit_7
AV 98
SNVT_time_hour
188
Analog Input
98
nvoSysDemand_7
AV 99
SNVT_time_hour
189
Analog Input
99
nvoHourOpt_7
AV 100
SNVT_time_hour
190
Analog Input
100
nvoSmallHrs_7
AV 101
SNVT_time_hour
191
Analog Input
101
nvoLargeHrs_7
AV 102
SNVT_lev_percent
192
Analog Input
102
Not Used
AV 103
SNVT_lev_percent
193
Analog Input
103
Not Used
AV 104
SNVT_lev_percent
194
Analog Input
104
Not Used
AV 105
SNVT_lev_percent
195
Analog Input
105
nviNetSensor_7
BV 91
SNVT_switch
196
Digital Output
91
Not Used
BV 92
SNVT_switch
197
Digital Output
92
Not Used
BV 93
SNVT_switch
198
Digital Output
93
nvoNetSensor_7
BV 94
SNVT_switch
199
Digital Input
94
nvoStatus_7
BV 95
SNVT_switch
200
Digital Input
95
nvoService_7
BV 96
SNVT_switch
201
Digital Input
96
nvoFault_7
BV 97
SNVT_switch
202
Digital Input
97
nvoInputType_7
BV 98
SNVT_switch
203
Digital Input
98
nvoConnection_7
BV 99
SNVT_switch
204
Digital Input
99
Not Used
BV 100
SNVT_switch
205
Digital Input
100
Not Used
BV 101
SNVT_switch
206
Digital Input
101
Not Used
BV 102
SNVT_switch
207
Digital Input
102
Not Used
BV 103
SNVT_switch
208
Digital Input
103
Not Used
BV 104
SNVT_switch
209
Digital Input
104
Not Used
BV 105
SNVT_switch
210
Digital Input
105