Nortec LINKS 2 NHRS User Manual
Page 25
Installation | 21
Table 5: Humidifier Variable Addresses - CONTINUED
BACnet
LonWorks
N2
Variables
Data
Type
Object
ID
SNVT Type
SNVT
Index
Data Type
Address
Unit 6 Variable Name
nviRHDem_6
AV 76
SNVT_lev_percent
151
Analog Output
76
nviSet_6
AV 77
SNVT_lev_percent
152
Analog Output
77
nviCapLimit_6
AV 78
SNVT_lev_percent
153
Analog Output
78
Not Used
AV 79
SNVT_lev_percent
154
Analog Output
79
Not Used
AV 80
SNVT_lev_percent
155
Analog Output
80
nvoRHDem_6
AV 81
SNVT_lev_percent
156
Analog Input
81
nvoSet_6
AV 82
SNVT_lev_percent
157
Analog Input
82
nvoCapLimit_6
AV 83
SNVT_time_hour
158
Analog Input
83
nvoSysDemand_6
AV 84
SNVT_time_hour
159
Analog Input
84
nvoHourOpt_6
AV 85
SNVT_time_hour
160
Analog Input
85
nvoSmallHrs_6
AV 86
SNVT_time_hour
161
Analog Input
86
nvoLargeHrs_6
AV 87
SNVT_lev_percent
162
Analog Input
87
Not Used
AV 88
SNVT_lev_percent
163
Analog Input
88
Not Used
AV 89
SNVT_lev_percent
164
Analog Input
89
Not Used
AV 90
SNVT_lev_percent
165
Analog Input
90
nviNetSensor_6
BV 76
SNVT_switch
166
Digital Output
76
Not Used
BV 77
SNVT_switch
167
Digital Output
77
Not Used
BV 78
SNVT_switch
168
Digital Output
78
nvoNetSensor_6
BV 79
SNVT_switch
169
Digital Input
79
nvoStatus_6
BV 80
SNVT_switch
170
Digital Input
80
nvoService_6
BV 81
SNVT_switch
171
Digital Input
81
nvoFault_6
BV 82
SNVT_switch
172
Digital Input
82
nvoInputType_6
BV 83
SNVT_switch
173
Digital Input
83
nvoConnection_6
BV 84
SNVT_switch
174
Digital Input
84
Not Used
BV 85
SNVT_switch
175
Digital Input
85
Not Used
BV 86
SNVT_switch
176
Digital Input
86
Not Used
BV 87
SNVT_switch
177
Digital Input
87
Not Used
BV 88
SNVT_switch
178
Digital Input
88
Not Used
BV 89
SNVT_switch
179
Digital Input
89
Not Used
BV 90
SNVT_switch
180
Digital Input
90