10 | Installation

BACnet/IP

A standard CAT-5E cable with an RJ-45 (Ethernet) jack is to be connected to port 3,4, or 5 on the
gateway. Refer to wiring diagrams in this manual.

Cable Shielding

The cable’s shield should be connected to the shield terminal at the BMS system only, and not the
Links 2 module.

As well the cable shield should be connected at the lead unit only and not at subsequent units.

For long chains the shield would appear as:

Unit 2 to Master - Shield connected at master only.

Unit 3 to Unit 2 - Shield connected at unit 2 only.

Unit 4 to Unit 3 - Shield connected at unit 3 only.

And so forth.

Gateway Configuration

Links2 is configured for each protocol at the factory, prior to final testing. Baud rates are adjusted
to the following values by default:

Table 3: Baud Rates

Protocol

Default Baud Rates

BACnet MS/TP

38.4 kbps

BACnet / IP

10BaseT

Johnson N2

9.6 kbps

LonWorks

38.4 kbps

Links2 packages require network addresses in order to communicate with a BMS system. In most
cases addresses information is factory configured during final testing. If the humidifiers were
ordered before BMS address information was available, Links2 would be figured to a default
address. Please contact the factory for the configuration tools to allow field modification of the
address parameters.