Nortec LINKS 2 NHRS User Manual
Page 20
16 | Installation
Table 5: Humidifier Variable Addresses
BACnet
LonWorks
N2
Variables
Data
Type
Object
ID
SNVT Type
SNVT
Index
Data Type
Address
Unit 1 Variable Name
nviRHDem_1
AV 1
SNVT_lev_percent
1
Analog Output
1
nviSet_1
AV 2
SNVT_lev_percent
2
Analog Output
2
nviCapLimit_1
AV 3
SNVT_lev_percent
3
Analog Output
3
Not Used
AV 4
SNVT_lev_percent
4
Analog Output
4
Not Used
AV 5
SNVT_lev_percent
5
Analog Output
5
nvoRHDem_1
AV 6
SNVT_lev_percent
6
Analog Input
6
nvoSet_1
AV 7
SNVT_lev_percent
7
Analog Input
7
nvoCapLimit_1
AV 8
SNVT_time_hour
8
Analog Input
8
nvoSysDemand_1
AV 9
SNVT_time_hour
9
Analog Input
9
nvoHourOpt_1
AV 10
SNVT_time_hour
10
Analog Input
10
nvoSmallHrs_1
AV 11
SNVT_time_hour
11
Analog Input
11
nvoLargeHrs_1
AV 12
SNVT_lev_percent
12
Analog Input
12
Not Used
AV 13
SNVT_lev_percent
13
Analog Input
13
Not Used
AV 14
SNVT_lev_percent
14
Analog Input
14
Not Used
AV 15
SNVT_lev_percent
15
Analog Input
15
nviNetSensor_1
BV 1
SNVT_switch
16
Digital Output
1
Not Used
BV 2
SNVT_switch
17
Digital Output
2
Not Used
BV 3
SNVT_switch
18
Digital Output
3
nvoNetSensor_1
BV 4
SNVT_switch
19
Digital Input
4
nvoStatus_1
BV 5
SNVT_switch
20
Digital Input
5
nvoService_1
BV 6
SNVT_switch
21
Digital Input
6
nvoFault_1
BV 7
SNVT_switch
22
Digital Input
7
nvoInputType_1
BV 8
SNVT_switch
23
Digital Input
8
nvoConnection_1
BV 9
SNVT_switch
24
Digital Input
9
Not Used
BV 10
SNVT_switch
25
Digital Input
10
Not Used
BV 11
SNVT_switch
26
Digital Input
11
Not Used
BV 12
SNVT_switch
27
Digital Input
12
Not Used
BV 13
SNVT_switch
28
Digital Input
13
Not Used
BV 14
SNVT_switch
29
Digital Input
14
Not Used
BV 15
SNVT_switch
30
Digital Input
15