Mounting the cm12 to a roof structure, Installation (cont.) – MovinCool CM12 User Manual
Page 9

9
INSTALLATION (cont.)
Mounting the CM12 to a Roof Structure
WARNING: Be sure that the supporting roof structure is capable of
supporting the weight of the unit, mounting hardware and the
accessories (Roof structure should be capable to support four
times of total weight or more. Unit weight is 123 lb (56 kg).
Be sure to securely anchor the top ends of the suspension rods. Make sure all nuts
are tight. Be sure to follow all applicable codes.
The CM12 unit is usually mounted above the ceiling and must be securely
mounted to the roof structure. The ceiling support of the existing building may
require reinforcements.
Use field-supplied threaded 1/2 inch suspension rods, washers, nuts and vibration
isolators.
The recommended clearance between ceiling grids and building the structural
member is the unit height plus 3.0 inch (76 mm).
ALL MOUNTING HARDWARE FIELD PROVIDED
Install the four field-supplied rods by
suspending them from suitable
building structure members. Locate
the rods so that they will align with
four mounting holes in the mounting
bracket that are part of the unit
base.
WARNING: Wear gloves to
avoid injury during
installation.
Tightening torque for nuts: 3.02
ft•lbf (4.1 N•m)
CAUTION: Make sure the
unit is level (must be less
than 2° incline).
1/2 in THREADED ROD
(MIN. 123 lb (56 kg) LOAD CAPACITY)
SEE MOUNTING DETAIL
VIBRATION ISOLATOR
(MIN. 123 lb (56 kg) LOAD CAPACITY)
1/2 in THREADED ROD
(MIN. 123 lb (56 kg)
LOAD CAPACITY)
1/2 in NUT
1/2 in WASHER
MOUNTING BRACKET
1/2 in WASHER
1/2 in NUT
1/2 in JAM NUT