INSTALLATION (cont.)

Power Connection

Connecting Power Supply to Unit

The following are recommended wire sizes

and electrical ratings:

• Cord Type: SJT (3 wires) or

equivalent

• Wire Gauge: 14 AWG
• Voltage Rating: 300 V minimum
• Heat Resistance: 140 °F (60 °C)

1. Remove service panel from the right

side of CM12 unit.

2. Route power cord wires through the

opening of the left grommet connector located below service panel. Tighten

the grommet connector at about 0.15 ft•lbf (0.2 N•m) torque.

3. Connect the neutral wire (white color label “R”) to the center screw connection

of terminal block. Tighten screw at about 0.96 ft•lbf (1.3 N•m) torque.

4. Connect the line wire (black color label “T”) to the left screw connection of

terminal block. Tighten screw at about 0.96 ft•lbf (1.3 N•m) torque.

5. Connect the ground wire (green color label “G”) to brass screw located below

terminal block. Tighten screw at about 0.96 ft•lbf (1.3 N•m) torque.

WARNING: All electrical work, if necessary, should only be

performed by qualified personnel. Repair to electrical components

by non-certified technicians may result in personal injury and/or

damage to the unit.

Drain Hose Connection

The CM12 is equipped with an internal

condensation removal pump. Maximum lift

is 4 feet (1.2 m).
1. Use the provided 1/2 inch (13 mm)

female connection on the unit for the

evaporator coil condensate drain. The

drain line must be located so it will not

be exposed to freezing temperatures.

The drain should be the full size of the

drain connection. (Connect the drain

hose to the condensation drain or the janitor closet.)

2. A 1/2 inch (13 mm) ID (5/8 inch (16 mm) OD), PVC tubing is required for the

drain. Insulate the drain hose; condensation may occur during humid

conditions. (Field supplied material)

T

R

G

POWER CORD

DRAIN PIPE

CONDENSATE PAN

DRAIN FOR MAINTENANCE