Check following items, Installation (cont.), Drain hose connection (cont.) – MovinCool CM12 User Manual
Page 12

12
INSTALLATION (cont.)
Drain Hose Connection (cont.)
Note: Do not use more than 4 feet (1.2 m) of drain hose vertically. This is maximum
lift of the condensation pump.
To insure proper drainage, locate the drain hose to the highest vertical position, no
more than 4 feet (1.2 m) high, and run the hose to the drain, run the drain hose on
a downward slope at a minimum rate of 1/4 inch (6 mm) per foot.
Check following items:
1. No kinks or bends on the drain hose
2. No trap in the drain hose
3. The end of the drain hose should be highter than the water level at the drain
4. No dripping from the drain hose at the clamping area
DRAIN HOSE ARRANGEMENT
When uninstalling the unit, empty the drain pan by draining out the water through
the drain pan drain pipe.
1. Plug in the 1/2 inch (13
mm) drain hose with the
lose clip into the drain
pipe. Make sure the hose
is all the way in and flush
with the grommet.
2. Position the clip to the top
of the drain pipe near the
unit as shown.
3. Pull out the red stopper and
secure hose. Make sure
there are no kinks or bends.
When using the gravity
drain, make sure the hose
is connected as a decline.
RED STOPPER
MAX. 3 ft
(0.9 m)
MAX. 4 ft (1.2 m)
1/4 inch (6 mm)
PER FOOT
OR MORE
CM12
SLOPE
ABOVE
DRAIN
WATER
NO TRAP
TO DRAIN HOSE
CM12
NO TRAP
NO POOL