Ducting with typical drop ceiling, Installation (cont.) – MovinCool CM12 User Manual
Page 16

16
INSTALLATION (cont.)
Ducting With Typical Drop Ceiling
Use a 10.0 inch diameter insulated duct with low friction and air resistance.
The duct should be bent in a large radius. If the bending radius is less than 15.0
inch (381 mm), then use vanes or guides to reduce air resistance.
Make sure the ducts are secured in order to absorb vibration from the unit.
Avoid bending the duct suddenly and have air ducts travel in a strait line for
improved performance.
• Following filed supplied hardware requires:
• Insulated 10.0 inch diameter ducts
• Return air grill with filter for evaporator air intake
• Diffuser for cold air
• Maximum external static pressure, 0.40 IWG (100 Pa) for evaporator duct and
grills
CAUTION: Do not operate CM12 without the filter installed on the
return air grill.
CONDENSER
INTAKE
CONDENSER
EXHAUST
COOL AIR SUPPLY
(EVAPORATOR)
ROOM AIR
INTAKE
2 ft x 2 ft,
T-bar diffuser
with 10.0 in flange
10.0 in insulated
flexible duct
(6 ~ 10 ft each)
2 ft x 2 ft,
T-bar return
grill with 10.0 in
flange and filter
RETURN GRILL WITH FILTER REQUIRED