INSTALLATION (cont.)

Ducting With Typical Drop Ceiling

Use a 10.0 inch diameter insulated duct with low friction and air resistance.

The duct should be bent in a large radius. If the bending radius is less than 15.0

inch (381 mm), then use vanes or guides to reduce air resistance.

Make sure the ducts are secured in order to absorb vibration from the unit.

Avoid bending the duct suddenly and have air ducts travel in a strait line for

improved performance.

• Following filed supplied hardware requires:

• Insulated 10.0 inch diameter ducts
• Return air grill with filter for evaporator air intake
• Diffuser for cold air

• Maximum external static pressure, 0.40 IWG (100 Pa) for evaporator duct and

grills

CAUTION: Do not operate CM12 without the filter installed on the

return air grill.

CONDENSER

INTAKE

CONDENSER

EXHAUST

COOL AIR SUPPLY

(EVAPORATOR)

ROOM AIR

INTAKE

2 ft x 2 ft,

T-bar diffuser

with 10.0 in flange

10.0 in insulated

flexible duct

(6 ~ 10 ft each)

2 ft x 2 ft,

T-bar return

grill with 10.0 in

flange and filter

RETURN GRILL WITH FILTER REQUIRED