beautypg.com

Fire alarm control panel connection (input signal), Connecting fire alarm control panel to cm12, Dip switch configuration and setting – MovinCool CM12 User Manual

Page 15: Installation (cont.)

background image

15

INSTALLATION (cont.)

Fire Alarm Control Panel Connection (Input Signal)

The CM12’s controller is equipped with a normal open input signal, which can be

connected directly from the fire alarm control panel. When receiving the signal

from the fire alarm control panel, the unit turns off and does not turn back on until

power source is reset or turns the wall thermostat off and on.

Connecting Fire Alarm Control Panel to CM12

1. Connect the fire alarm signal wires to CM12 signal wires label E+ and E-.

2. Use recommended fire alarm signal wire size from 16 AWG to 26 AWG for a

solid wire, or 16 AWG to 22 AWG for a stranded wire.

DIP Switch Configuration and Setting

The CM12’s controller is equipped with a 4-position DIP switch, which defaults in

the OFF position. The DIP switch can be set to configure the following functions:

a. When the switch position #1 is ON, the evaporator and condenser fan

motor turn on. This function is used for test purposes and verification.

b. When switch position #2 is ON, the compressor, evaporator and condenser

fan motor turn on. This function is used for test purposes and verification.

c. When switch position #3 is ON, the compressor delay timer function is

disabled.

d. When switch position #4 is ON, the buzzer sound function is disabled.

12

3

4

NO

“OFF” POSITION

250V 5A

OUTPUT

: 12.6V

-0.37A

GA09301-G ST

INPUT

: 230V 1

15V 0

CN01

CN15

CN16

CN14

CN02

CN03

CN04

CN17

CN25

CN23

CN22

CN21

4

3

52CH

RT

S

CTS

ODS

SW2

4-POSITION DIP SWITCH