Power Supply Requirements

• The CM12 requires a single-phase 115 V, 60 Hz power supply to operate.
• The power supply should be a dedicated single outlet circuit with a UL approved

short-circuit and ground fault protective breaker with a fuse size of 20 A maximum.

Service Panel Access

1. Access service panel by

removing 4 screws.

Tightening torque for screw: 1.10

ft•lbf (1.5 N•m)

2. Remove the service panel.

CIRCUIT BREAKER WITH
GROUND-FAULT PROTECTIVE

FUSE 20 A MAX.

R

T

G

R

T

G

TERMINAL BLOCK OF CM12

GROUND TERMINAL